Trouble chart contintued – Midco 400B-02 User Manual

Page 12

Advertising
background image

A.

Manual Gas Cock Knob on Combination Valve not in ON position.

B.

Check for 24V* between blower interlock switch terminal NC and GND;

1. If no voltage, motor interlock switch or centrifugal actuator is defective. (See Section X

Blower Assembly).

2. If voltage is present, valve operator is defective; entire valve must be replaced.

A.

Low manifold gas pressure.

B.

Main gas spud orifice too small.

C.

Primary air adjustment open too far.

A.

High manifold gas pressure.

B.

Main gas spud orifice too large.

C.

Primary air adjustment closed too far.

D.

Dirty Blower Wheel

A.

Electric Valve Operator(s) of Combination Valve is defective and entire valve must be

replaced.

* Normal low voltage:

Motor running-24V minimum
Combination Valve energized-21V minimum.

** IMPORTANT: If changes are made in the main spud orifice size manifold gas pressure or pri-
mary air adjustment, change the installation data tag accordingly.

12

IV. Motor Runs

Continuously, Pilot is On,

But No Main Flame

V. Short Flame**

VI. Long, Hazy Flame**

VII. Gas Fails to Shut Off

Trouble Chart Contintued