12. The actual NATURAL gas firing rate in BTU per hour

can be determined by timing the gas meter. Accurately
time the meter test dial for one revolution, convert to
hourly cubic feet and multiply by the BTU per cubic foot
value of your gas per formula:

Then divide by 1,000 for MBH value.

13. Start and stop the burner several times to check its

operation with the charging door open, and then with
it closed. Remove any temporary Door Open bypasses
installed in Step 6.

14. Test operation of any auxiliary operating and/or limit

controls.

15. Load incinerator and make trial run. Confirm that the

incineration chamber pressure stays within the range of
0 to minus 0.5"W.C. for Model J81A-3 and 0 to minus
1.0” W.C. for Model J121A-3.

16.

WARNING: When the incinerator is located

inside a building and a draft control is used, check
that there is no spillage of flue products from the draft
control.
17. To shut off: Turn Burner Switch or Timer off and close

Main Manual Shut -Off Valve

PART 1

SERVICE

WARNING: BE SURE THAT THE MANUAL VALVE AND

BURNER DISCONNECT SWITCH ARE TURNED OFF BEFORE

ANY PARTS ARE REMOVED FOR SERVICE.

VIII

IGNITOR AND REGULATOR ASSEMBLY

The Ignitor and Regulator Assembly is removed as a unit.
Disconnect the ignitor gas line and electrode wires, remove
the two mounting screws and pull out the assembly.

When the ignitor gas pressure is in the proper range (see

Table 4) and the electrodes are adjusted to the dimensions
shown in Figure 5, any ignition problems are usually
caused by lint, dust, corrosion, cracked electrode
insulators, foreign matter in the blast tube or deterioration of
ignitor ports in Retention Plate.

Ignitor trouble will be evidenced by failure of main burner

ignition. It may also be indicated by poor or erratic relay
response which cannot be remedied by ignitor gas
adjustment, or it may cause frequent Flame Safeguard
lockout. Check for dirt in the ignitor air and mixture
passageways and check for obstructions in the ignitor
ports. Also check electrode adjustments (see Figure 5).
Replace any severely burned parts.

Proper operation of the flame sensor rod can be checked

by measuring the flame signal. With the Flame Safeguard
energized and only the ignitor burning, a good reading
should run steady 2 or more volts DC.

When servicing, clean the Ignitor Retention Plate ports

and blow out the internal air and gas passages. Clean the
Electrode Insulators and check them for hairline cracks.
Also check the electrode ends and the Ground Barrier for
serious corrosion or loss of metal. Replace any defective
parts.

Make sure that there is no debris in the Blast Tube that

could short out the Spark or Flame Electrode.

Clean the Ignitor Gas Orifice in Tee Orifice Fitting (see

Figure 5) and check that the orifice size is correct per Table
4.

TABLE 4

Ignitor Firing Rate

Q7800 BASE FOR
RM7890 FLAME
SAFEGUARD

G

5

20

21

6

7

8

F

3

4

9

10

19

18

17

16

22

15

14

13

L2

12

L2 3 4 5 6 7 8 9 10 11

NEUTRAL

120/1/60

HOT

4

5

6

1

2

3

MAIN GAS VALVE

OPTIONAL
REDUNDANT VALVE

OPTIONAL VENT
VALVE

BLOWER MOTOR

NO

NC

C

SAFETY & OPERATING

CONTROLS

FLAME ROD

SPARK ROD

3 2 1

THERMAL
SWITCH

THERMAL SWITCH

OPTIONAL HI-LO GAS PRESSURE
SWITCH. IF USED, REMOVE
JUMPER 3-4

L2

L1

BK

3

10

Y

3

4

R/W

1

2

3

8

10

9

F

6

7

8

W(BK)

IGNITOR GAS VALVE

BR

BL

BL

BL/W

BK(W)

O

9

Y/BK

BK

W

L2

6

HOT

120/1/60

NEUTRAL

SCHEMATIC

FUSED DISCONNECT

TERMINAL STRIP

SAFETY & OPERATING

CONTROLS

COMPONENT LAYOUT

Y/W

SWITCH OR TIMER

(LINE VOLTAGE)

(LINE VOLTAGE)

J81A-3 MOTOR END SWITCH
J121A-3 BLOWER AIR SWITCH

5

R

BL/W

Y/W

SPARK GENERATOR

R/BK

L2

L1

L

R/BK

IF NOT USED JUMPER
10 TO 3

FIGURE 2

Wiring Diagram

CAUTION: If a remote switch or timer is installed, remove or turn off the burner switch when using the remote control

TYPE

OF

GAS

NATURAL

PROPANE

NATURAL

PROPANE

IGNITOR

GAS

RATE

6 MBH
7 MBH

13 MBH
15 MBH

IGNITOR

ORIFICE

DIAMETER

.052 (#55 Dr.)
.042 (#58 Dr.)

.070 (# 50 Dr.)

.063 (#52 Dr.)

RECOMMENDED

IGNITOR GAS

PRESSURE

3.5 "W.C.

-6-

3600 x Test Dial Size x BTU Value
No. of Seconds for One Rev. Test Dial

= BTU/Hr.

Example: 3600 x 1 x 1000*

20

*Approximate BTU value.

=180,000 BTU/ Hr. = 180 MBH