Trouble chart – Midco J83-DS User Manual

Page 11

Advertising
background image

A.

With motor running check burner line voltage terminals for 120V as follows:

1. Between strip terminals L1 and L2 - 120V: voltage OK.
2. Between strip terminals L1 and GND.TERM - 120V: ground OK.
3. Between strip terminals L2 and GND.TERM. - no voltage: no backfeed neutral

OK.

B. Follow test procedure as specified in Step II G.

1. Connect DC microamp meter in series with sense wire and Electronic Control

SENSE terminal. With flame on, flame signal should be steady and at least 2
microamps. Check sense wire for continuity Adjust ignitor gas pressure to
obtain acceptable signal and note gas pressure and signal strength for future
reference.

A. Low gas pressure
B. Air shutter open too far
C. Input adjuster not set properly

A. High gas pressure
B. Air shutter closed too far
C. Insufficient free air in combustion chamber
D. Dirty blower wheel
E. Input adjuster not set properly

A. Defective automatic valve
B. High gas pressure

*Normal low voltage:

Motor running - 24V minimum
Automatic valve energized - 21V minimum

Trouble Chart

III Flame on Only

During 6-Second
Trial for Ignition

IV Short Flame

V

Long Hazy Flame

VI Gas Fails to Shut

Off

11