CHAPTER 16: FAIL – SAFE SYSTEM


16.1 Overview

The Fail-Safe System is a set of features that allow an application to continue running in the event of
certain types of "soft" failures. These "soft" failures include:

•

Battery power loss

•

Battery-Backed Register RAM or Application Flash corruption due to, for example, an excessive
EMI event.


The Fail-Safe System has the following capabilities:

•

Manually backup the current Battery-Backed RAM Register Settings into Flash memory.

•

Manually restore Register Settings from the values previously backed up in Flash to Battery-
Backed RAM.

•

Detect corrupted Register Settings at power-up and then automatically restore them from Flash.

•

Detect corrupted or empty application in Flash memory at power-up and then automatically load
the AUTOLOAD.PGM application file from Removable Media (Compact Flash or MicroSD).

•

If an automatic Register Restore or Application Load occurs, the OCS can automatically be
placed in RUN mode


The fail-safe system can be accessed by going to the system menu of the controller. A new menu “Fail-
Safe System” has been added at the end of the main system menu for this. Selecting “Fail-Safe System”
menu will open the following menu screen:

Figure 16.1 – Fail – Safe System Menu