Figure 16.3 – Backup Registers
Restore OCS Data:
When initiated, this will allow the user to manually copy the backed up data from the onboard FLASH to
the Battery-Backed RAM.
A restore operation will be automatically initiated if a backup has been previously created and on power-
up the Battery-Backed RAM registers fail their check.
The following process will be followed for restoring data:
•
The controller will be placed in IDLE mode.
•
Data will be copied from onboard FLASH to OCS Battery-Backed RAM
•
The controller will reset.
•
The controller will be put in RUN mode if the AutoRun setting is ‘Yes’ else it will remain in IDLE
mode.
Figure 16.4 – Restore OCS Data
%SR164.3 is set to 1 only when an automatic restore operation is performed - not on a manual one. This
bit is reset to 0 when a new backup is created.