Specifications

Specifications

ADC170

Number of Channels

4

Input Ranges

0-10V, 4-20mA, 0-20mA

Absolute Max. Inputs

+/-15V, +/-30mA

Resolution

12-Bit (2.5mV, 4uA, 5uA)

Input Impedance

1MΩ (voltage), 250Ω (current)

Accuracy

< +/-0.5%

Isolation

Photocoupler (Input/Power)

Conversion Time

1.5mS/ch

Backplane Power Consumed

50mA @ 5V

External Power Required

62mA @ 24V (+/-10%)

Terminal Type

Screw Type, Removable 11-posn

Optional Spring-clamp Plug

HE599TRM011

Storage Temp.

-25° to 70° Celsius

Operating Temp.

-0° to 55° Celsius

Relative Humidity

5 to 95% Non-condensing

Dimensions WxHxD

20mm x 90mm x 60mm

0.79” x 3.54” x 2.36”

Weight

67g (2.4 oz.)

CE & UL Compliance

CE, UL & C-UL


2

Wiring – I/O








3

Configuration DATA


The SmartRail ADC170 features a dip switch on the front of the unit for selecting voltage (0-10V) or
current (4-20mA or 0-20mA) on a per channel basis. In addition to the physical dip switch, Cscape
(9.1 or later) must be used for software configuration as well. The following parameters are
configurable in Cscape for the ADC170:

Cscape Configuration Data – Selectable per channel

Parameter

Selections

Enable

Channel Enable

Disable

4-20mA
0-20mA

Data Type

0-10V

0-4000

-2000 to +2000

0 to 1000 (for 4-20mA type)

Data Range

0 to 1000 (0-20mA or 0-10V type)






4

Installation / safety






a. All applicable codes and standards should be followed in the installation of this product.
b. Shielded, twisted-pair wiring should be used for best performance.
c. Shields should be grounded at one end only, preferably at the end providing the best noise
shunting.
d. Use the following wire type or equivalent: Belden 8441.

For detailed installation and a handy checklist that covers panel box layout requirements and
minimum clearances, refer to the hardware manual of the controller you are using.

When found on the product, the following symbols specify:






7

Technical Support

Technical Support at the following locations:

North America:
Tel: 317 916-4274
Fax: 317 639-4279
Web:

http://www.heapg.com

Email:

[email protected]

Europe:
Tel: +353-21-4321266
Fax: +353-21-4321826
Web:

http://www.horner-apg.com

Email:

[email protected]







ADC170 LED Status Indication

LED

Meaning
ON = Normal Operation
FLASH = I/O Error

RUN

OFF = No Power or I/O Error

SmartRail

0-10V, 4-20mA Analog Input Module

HE599ADC170

12-Bit Resolution

No part of this publication may be reproduced without the prior agreement and written
permission of Horner APG, Inc. Information in this document is subject to change without
notice.

Warning: Remove power from the OCS controller and any peripheral equipment connected
to this local system before adding or replacing this or any module.

Warning: Consult
user documentation.

Warning: Electrical
Shock Hazard.

+

-

24VDC

N.C.

-

CH4

+

-

CH3

+

-

CH2

+

-

CH1

+

CH1

CH2

CH3

CH4

V

I

24VDC @ 62mA
External Power

SHIELD GROUNDED
AT ONE END ONLY

0-10V

0-10V

+

+

+

-

-

-

LOOP
POWER

4-20ma

+

-

+

-

LOOP
POWER

4-20ma

+

-

+

-

Prefer Spring-clamps?

Optional Spring-clamp style plugs are
available as economical wiring accessories.
See specification table for part number(s).