Horner APG SmartBlock User Manual

Smartblock i/o module, Specifications, Can wiring

Advertising
background image

MAN0980-01-EN

Specifications/Installation

10/29/2013

No part of this publication may be reproduced without the prior agreement and written permission of Horner APG, LLC. Information in this document is subject to change without notice.

Page 1 of 5

SmartBlock I/O Module

HE579DIQ880 ‒ 8DC Inputs, 8 Relay Outputs

HE579DIQ881 - 8DC Inputs, 8 DC Outputs

1. SPECIFICATIONS

DIQ880 & DIQ881 Digital DC Inputs

DIQ880 Digital Relay Outputs

Inputs per Module

8

Outputs per Module

8 relay

Commons per Module

1

Commons per Module

8

Input Voltage Range

12 VDC / 24 VDC

Max. Output Current per Relay

3A @ 250 VAC, resistive

Absolute Max. Voltage

35 VDC max.

Max. Total Output Current

25A continuous

Input Impedance

10KΩ

Max. Output Voltage

275 VAC, 30 VDC

Input Current

Positive Logic

Negative Logic

Response Time

Network Time + 10ms

Current Max. Upper Threshold

0.8mA

-1.6mA*

Max Switched Power

1250VA, 150W

Current Min. Lower Threshold

0.3mA

-2.1mA*

Contact Isolation to Bus/Ground Power

1000 VAC

Voltage Max. Upper Threshold

8 VDC

Max. Voltage Drop at Rated Current

0.5V

Voltage Min. Lower Threshold

3 VDC

Expected Life

No load: 5,000,000

Rated load: 100,000

DIQ881 Digital DC Outputs

Max. Switching Rate

300 CPM @ no load

20 CPM @ rated load

Outputs per Module

8

Commons per Module

1

Type

Mechanical Contact

Output Type

Sourcing, active pull-down

Max. Output Current per Point

2.5A

General Specifications

Max. Total Output Current

10A

Voltage Input (V+)

10-30 VDC

Output Supply Voltage (VS)

9-30VDC

Relative Humidity

5 to 95% non-condensing

Response Time

Network Time + 10ms

Required Power (Steady State)

2W (80mA @ 24 VDC)

Voltage Drop @ Rated Current

1V

Required Power (InRush)

DC Switched: 12A 50μS

AC Switched: 120mA 10ms

Protection

Short circuit, Overtemp,

Automatic Reset


Operating Temperature

0⁰ to 60⁰ C

Max. Switching Rate

Limited by message rate

Weight

12 oz. / 340 g

*24VDC Supply Voltage


NOTES:

A. I/O common pins, C, are internally connected to the power supply negative.
B. Digital inputs are configurable for positive or negative logic using Cscape.
C. When configured for positive logic, the inputs are pulled down to common by a 10K resistor. When an input is open or low, the

associated LED is OFF and the associated OCS register bit is 0. When an input is driven high above the threshold level, the
associated LED turns ON, and the associated OCS register bit is 1.

D. When configured for negative logic, the inputs are pulled up to the positive supply voltage, V+, by a 10K resistor. When an

input is open or high, the associated LED is OFF and the associated OCS register bit is 0. When an input is driven low, below
the threshold, the associated LED turns ON, and the associated OCS register bit is 1.

2. CAN Wiring

CAN Network & Power Connector
Torque rating 4.5

– 7 Lb.-In. (0.50 – 0.78 N-m

)

Network, Power, and Grounding:
A single 5 pin connector is used to make both a network connection and power input. A quality class 2 power supply should be used for
this product. If the power is run with the network cable, care must be taken such that the voltage does not drop below the lower supply
limit on longer runs.

A quality earth ground is required for safe and proper operation. The best ground is achieved by screwing the lower left grounding
location into a grounded back plate. Alternately, a ground can be connected to the spade lug.
Please see Horner manual MAN0799 for details on CAN wiring.

CAN Network & Power Port Pin Assignments

Pin

Signal

Signal Descriptions

Direction

1

V‒

CAN & Device Ground – Black

2

CN_L

CAN Data Low - Blue

In/Out

3

SHLD

Shield Ground - None

4

CN_H

CAN Data High - White

In/Out

5

V+

Positive DC Voltage

Input (10-30 VDC) - Red