Install the Lamps

Connect the neutral power line wire to the white fixture wire

marked “COM” with a wire nut.

Connect the

hot power line wire to the black

switched

fixture wire marked “SWITCHED HOT” with a wire nut.

Connect the

hot power line wire to the black

unswitched

fixture wire marked “ALWAYS HOT” with a wire nut.

Connect the red test switch wire to the loose red fixture wire

with a wire nut. Connect the white test switch wire to the

loose red/white fixture wire with a wire nut.

Plug the white/black unit connector wires together.
CAUTION: RISK OF SHOCK! Plug these wires in only

after all other connections have been made.

Reinstall the reflector into the housing and tighten all six

screws to hold it in place. Place the reflector so the end

marked “THIS SIDE UP” is at the top.

Medium

MAX 17 Watt

versions use

type T8 linear

fluorescent lamp.

versions use

type T8 linear

Large

MAX 25 Watt

fluorescent lamp.

Line up the lamp pins on both ends with the opening on the

sockets.

Insert the pins all the way into the sockets and turn the lamp

to lock it in place.

Reinstall the front cover on to the housing and fully tighten all

six cap screws. Tighten all the cap screws evenly to prevent

the cover from flexing, which could cause the glass to break.