Low output voltage, Load led bar flash, And voltage indicator – Samlex America SA-1500 User Manual

Page 19: In lower red zone, Over temp indicator, On, load less than, 1500w, No output voltage, Over load indicator, Troubleshooting guide

Advertising
background image

17

4. Troubleshooting guide

Problems and Symptoms

Possible Cause

Solutions

Low output voltage

Using average reading
voltmeter

Use true RMS reading meter

and cable.

See page 15

Point 3-7-7. of manual

Load LED bar flash

Overload

Reduce load.

No output voltage

Low input voltage

Recharge battery,

And voltage indicator

check connections

in lower red zone

and cable.

No output voltage

Thermal shutdown

Improve ventilation,

Over Temp indicator

Make sure ventilation

on, load less than

openings in inverter

1500W.

are not obstructed.

Reduce ambient

temperature.

No output voltage,

Short circuit or Wiring Check AC wiring

Over Load indicator

error

for short circuit or

On

improper polarity (hot

and neutral reversed).

Very high power load Remove load