RIM-Protocol Converter User Guide - Version 1.0

Chatsworth Products, Inc. (CPI) • 800-834-4969

29

3.5

Configure Slave Devices

Once the basic functionality of the Protocol Converter has been configured, you’re ready to configure slave devices. You can configure
up to 32 slave devices to the Protocol Converter.

1. From the top navigation bar on the Protocol Converter’s home page, click the Device Configuration link.

The Device Configuration page is divided into four subpages - eight slave devices can be configured on each page. These slave devices
can be configured for Modbus RTU/485, Modbus TCP, SNMP V1, BACnet/IP, SNMP-RFC1628, or SNMP V2C.

Figure 3.11 Device Configuration Screen

2. To configure a slave device, enter the appropriate information for the communication protocol used by that device. Only the

applicable fields for each communications protocol will appear. Configurable fields include:

Table 3.4 Device Configuration Fields

Option

Description

Access Mode

Use the drop-down to select Modbus-RTU/485, Modbus
TCP, SNMP V1, BACnet/IP, SNMP-RFC-1628, or SNMP
V2. Note: RFC-1628 access mode is available for BACnet/IP only.

EIA-485 Port

Select the appropriate port.

Modbus/TCP Poll Rate

Select the number of packets per second - 10, 5, or 1.