P ow erS cope U ser M anual R ev. X 1

A ugust 1, 2009

14

Gateway: Contains the IP address of the network’s gateway PowerScope in the
form of xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254.

AutoIP: Check if the Inline Scope is having the IP address assigned by DHCP
server. Not recommended.

Host: Check if SNMP traps are to be sent to specific SNMP Host address. If
checked, at least one of the 3 SNMP Host Addresses below has to be filled in.

WEB: Check to enable standalone WEB GUI mode.

SWU: Check to enable software update.

SNMP Host Address: Contains the assigned IP address for the PowerScope in
the form of xxx.xxx.xxx.xxx, where xxx is a number from 1 to 254 of the Host(s)
that the SNMP traps will be sent to.

PDU Name: Name assigned to this PowerScope, the maximum number of
characters that can be entered is less than 32.

PDU Password: Holds the password used by the PowerScope to access SEMA.
This is a protected variable accessible only by SEMA.

SEMA Name: Name of the SEMA group that this PowerScope belongs to. This
is a protected variable accessible only by SEMA.

SEMA Password: Holds the password used by SEMA to access this
PowerScope. This is a protected variable accessible only by SEMA.

Min Temperature: Set the low temperature threshold (in degrees Fahrenheit) that
when reached the PowerScope will send notification to SEMA over network. If
this variable is set to 0 the notification is disabled. Maximum value that should
be entered is 199.

Max Temperature: Set the high temperature threshold (in degrees Fahrenheit)
that when reached the PowerScope will send notification to SEMA over network.
If this variable is set to 0 the notification is disabled. Maximum value that should
be entered is 199.

Min Humidity: Set the low humidity threshold (in %) that when reached the
PowerScope will send notification to SEMA over network. If this variable is set to
0 the notification is disabled. Maximum value that should be entered is 100.

Max Humidity: Set the high humidity threshold (in %) that when reached the
PowerScope will send notification to SEMA over network. If this variable is set to
0 the notification is disabled. Maximum value that should be entered is 100.


Maximum Current: Is the value (in Amps) that when the branch circuit
consumption is reached the PowerScope will send alert to SEMA. If this variable