Campbell Scientific 4WFBS120, 4WFBS350, 4WFBS1K 4 Wire Full Bridge Terminal Input Modules User Manual

Page 19

Advertising
background image

4WFBS120, 4WFBS350, 4WFBS1K 4 Wire Full Bridge Terminal Input Modules (TIM)

12: Average (P71)
1: 1

Reps

2: 4

Loc [ uStrain ]


*Table 2 Program
2: 0.0000

Execution

Interval

(seconds)


*Table 3 Subroutines

1: Beginning of Subroutine (P85)

;Subroutine to measure "zero"

1: 1

Subroutine

1


2: Do (P86)

;This prevents calling subroutine

1: 11

Set Flag 1 High

;until user sets flag 1 low again.


3: Z=F (P30)

;Set counter use for average to 0

1: 0

F

2: 0

Exponent

of

10

3: 5

Z Loc [ Count ]


4: Z=F (P30)

;load 4 million (4*uS/S) into input location

1: 4

F

2: 6

Exponent

of

10

3: 7

Z Loc [ _4e6 ]


5: Z=F (P30)

;Load Gage Factor into input location

1: 2

F

;Enter the actual Gage Factor here

2: 0

Exponent

of

10

3: 6

Z Loc [ GF ]


6: Z=X/Y (P38)

;calculate multiplier to use with strain

1: 7

X Loc [ _4e6 ]

;calculation

2: 6

Y Loc [ GF ]

3: 8

Z Loc [ Mult ]


7: Beginning of Loop (P87)

;Loop through 5 times to obtain average

1: 0

Delay

;zero reading

2: 5

Loop

Count


8: Z=Z+1 (P32)

;Increment Counter used to determine

1: 5

Z Loc [ Count ]

;when to output


9: Full Bridge (P6)

;Measure Strain Gage

1: 1

Reps

2: 22

± 7.5 mV 60 Hz Rejection Range

3: 1

DIFF

Channel

4: 1

Excite all reps withExchan 1

5: 2500

mV

Excitation

6: 1

Loc [ mVperV ]

7: 1

Mult

8: 0

Offset


10: IF (X<=>F) (P89)

;Check for last pass through loop

1: 5

X Loc [ Count ]

;to set output flag

2: 3

>=

3: 5

F

4: 10

Set

Output

Flag

High


11: Set Active Storage Area (P80)

;Direct averaged "zero" reading

1: 3

Input

Storage

Area

;to input storage

2: 2

Array ID or Loc [ mVperV_0 ]

13