characters are typed within 60 seconds, then the mode is exited. In that

case, simply enter the command SDI12 again, press <enter>, and key in

the correct control port number when prompted.

6. To change the SDI-12 address, key in

aAb! <enter>, where a is the current

address from the above step and b is the new address (see FIGURE D-2).

The CS451/CS456 will change its address and the datalogger will respond

with the new address. To exit SDI-12 transparent mode, select the

Close

Terminal button.

FIGURE D-2. CR1000 example of using the SDI-12 transparent mode

to change the SDI-12 address from 3 to 1. Sensor is connected to

control port 1.

D.3 Advanced SDI-12 Commands

Extended SDI-12 commands can be used to configure the CS451/CS456 data

output and sample number. To query the sensor for the configuration, use the

aV! command followed by the aD! command.

The extended commands are used to select the temperature units (Celsius or

Fahrenheit), pressure/level units (psig, kPa, bar, feet, meter, inches, or

millimeter), and the integration time for each measurement. If level units are

selected, they will represent level of fresh water. The multiplier (slope) and

offset should be used to correct for relative density of water.

Sample number represents the number of values used to provide the output

value received by the datalogger. This output value is an average of the

samples.

The extended SDI-12 command used to configure output units is

aXCONFIG1=tt,pp,mmm.mm,ooo.oo! where a = the SDI-12 address of the

sensor, tt = temperature units, pp = measurement unit, mmm.mm = multiplier

(slope), and ooo.oo = offset.

Valid entries for tt (temperature) are:

0 = Celsius

1 = Fahrenheit