Campbell Scientific SDM-CD16AC 16-Channel ac/dc Relay Controller User Manual

Page 22

Advertising
background image

SDM-CD16AC 16 Channel AC/DC Controller

21: End (P95)

End Then Do/Else/End


END COOLER CONTROL LOGIC

START FAN CONTROL LOGIC BASED ON HEATER/COOLER

22: If X<=>F (P89)

If heater is on

1: 10--

X

Loc

2: 2

<>

3: 0

F

4: 11

Set high Flag 1

Set flag 1


23: If X<=>F (P89)

If cooler is on

1: 15--

X

Loc

2: 2

<>

3: 0

F

4: 11

Set high Flag 1

Set flag 1


24: If Flag/Port (P91)

If flag 1 is set

1: 11

Do if flag 1 is high

2: 30

Then

Do

Then


25: Z=F (P30)

Put a "1" into fan

1: 1

F

control location

2: 0

Exponent of 10

3: 20--

Z

Loc:


26: Else (P94)

Else, If flag 1 is reset


27: Z=F (P30)

Put a "0" into fan

1: 0

F

control location

2: 0

Exponent of 10

3: 20--

Z Loc :


28: End (P95)

End Then Do/Else/End


29: Do (P86)

Reset flag 1

1: 21

Set low Flag 1


30: End Loop (P95)

End Master Loop


END FAN CONTROL LOGIC BASED ON HEATER/COOLER

START FAN CONTROL LOGIC BASED ON TIME

31: If time is (P92)

If 5 minutes remain

1: 10

minutes into a

out of 15 minute

2: 15

minute

interval

interval,

3: 12

Set high Flag 2

set flag 2

18