VDIV10.1, VDIV2.1 Voltage Divider Terminal Input Modules

The following examples show the measurement instruction for each of the
different dataloggers to measure the battery voltage described above.

4.1.1 CR1000, CR800, CR850

Public BattVolt
VoltDiff (BattVolt,1,mV2500,1,True ,0,250,0.01,0)

4.1.2 CR3000, CR5000

Public BattVolt
VoltDiff (BattVolt,1,mV5000,1,True ,0,250,0.01,0)

4.1.3 CR9000(X)

VoltDiff(BattVolt, 1, mV5000, 5, 1, 1, 0, 0, 0.01, 0)

4.1.4 CR7

1: Volt (Diff) (P2)
1: 1

Reps

2: 7

± 1500 mV Slow Range

3: 1

In

Card

4: 1

DIFF

Channel

5: 1

Loc [ BattVolt ]

6: 0.01

Mult

7: 0

Offset

4.1.5 CR10(X)

1: Volt (Diff) (P2)
1: 1

Reps

2: 25

± 2500 mV 60 Hz Rejection Range

3: 1

DIFF

Channel

4: 1

Loc [ BattVolt ]

5: 0.01

Mult

6: 0

Offset

4.1.6 CR23X

1: Volt (Diff) (P2)
1: 1

Reps

2: 15

5000 mV, Fast Range

3: 1

DIFF

Channel

4: 1

Loc [ BattVolt ]

5: 0.01

Multiplier

6: 0

Offset