American Dryer Corp. MLG-130DR (HSI) User Manual

Page 20

Advertising
background image

16

a. Outside Duct Work Protection

1) To protect the outside end of horizontal duct work from the weather, a 90° elbow bent downward

should be installed where the exhaust exits the building. If the duct work travels vertically up

through the roof, it should be protected from the weather by using a 180° turn to point the opening

downward. In either case, allow at least twice the diameter of the duct between the duct opening

and the nearest obstruction.

IMPORTANT: DO NOT use screens or caps on the outside of opening of exhaust duct work.

2. Single Dryer Venting

Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct should

be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns

as possible. It is suggested that the use of 90° turns in the ducting be avoided; use 30° and/or 45° angles

instead. The shape of the exhaust duct work is not critical so long as the minimum cross section area is

provided.

IMPORTANT: Minimum duct size for a dryer is 12-inches (30.48 cm) for a round duct 10-3/4” x

10-3/4” (27.31 cm x 27.31 cm) for a square duct. THE DUCT SIZE MUST NOT

BE REDUCED ANYWHERE DOWN STREAM OF THE DRYER.

IMPORTANT: Exhaust back pressure measured by a manometer at each tumbler (basket) exhaust

duct area should not exceed 0.3 inches of water column (0.74 mb).

Advertising