Important – Allied Air Enterprises WARM AIR GAS FURNACE 92G1UH User Manual

Page 17

Advertising
background image

506724-01

Page 17 of 57

Issue 1108

Vent Piping Guidelines

This gas furnace can be installed as either a Non-Direct

Vent or a Direct Vent gas central furnace.

NOTE: In non-Direct Vent installations, combustion air is

taken from indoors and flue gases are discharged outdoors.

In Direct Vent installations, combustion air is taken from

outdoors and flue gases are discharged outdoors.

Intake and exhaust pipe sizing - Size pipe according to Tables

4 and 5. Table 4 lists the minimum vent pipe lengths

permitted. Table 5 lists the maximum pipe lengths permitted.

Regardless of the diameter of pipe used, the standard roof

and wall terminations described in section Exhaust Piping

Terminations should be used. Exhaust vent termination pipe

is sized to optimize the velocity of the exhaust gas as it exits

the termination. Refer to Table 6.

In some applications which permit the use of several different

sizes of vent pipe, a combination vent pipe may be used.

Contact Allied Air Technical Service for assistance in sizing

vent pipe in these applications.

NOTE: It is acceptable to use any pipe size which fits within

the guidelines allowed in Table 5.

NOTE: The exhaust collar on all models is sized to

accommodate 2” Schedule 40 vent pipe. In horizontal

applications, transition to exhaust pipe larger than 2” must

be made in vertical runs of the pipe. A 2” elbow must be

added before the pipe is transitioned to any size larger than

2”. This elbow must be added to the elbow count used to

determine acceptable vent lengths. Contact the Application

Department for more information concerning sizing of vent

systems which include multiple pipe sizes.

Do not use screens or perforated metal in exhaust or

intake terminations. Doing so will cause freeze-ups and

may block the terminations.

IMPORTANT

FIGURE 20

12" max

of straight pipe

Exhaust Pipe

12" Min.

NOTE − Exhaust pipe MUST be glued to furnace exhaust fittings.

NOTE

− All horizontal runs of exhaust pipe must slope back to-

ward unit. A minimum of 1/4" (6mm) drop for each 12" (305mm)
of horizontal run is mandatory for drainage.

NOTE − Exhaust piping should be checked carefully to make
sure there are no sags or low spots.

Horizontal Application

Use the following steps to correctly size vent pipe diameter.

1

2

3

4

5

6

045, 070,
090, 110
or 135 btuh

Which termination?

Standard or
Concentric?
See table 3

Intake or
exhaust

Which needs
most elbows?

How many?

2", 2 1/2",
3" or 4"

Desired pipe size?

Use table 5 to find
max. intake or
exhaust pipe length.

FIGURE 21

What is the altitude?

7

Furnace capacity?

TABLE 4

MINIMUM VENT PIPE LENGTHS

A95UH/A93UH/95G1UH &93G1UH

MODELS

MIN. VENT LENGTH*

045, 070, 090, 110

15 ft. or

5 ft plus 2 elbows or

10 ft plus 1 elbow

135**

*Any approved termination may be added to the minimum length listed.
**This gas furnace must have 3” to 2” reducing ell (supplied or field
replacement Canadian kit) installed directly into unit flue collar.

Advertising
This manual is related to the following products: