Details of Intake and Exhaust Piping Terminations for

Direct Vent Installations

NOTE: In Direct Vent installations, combustion air is taken

from outdoors and flue gases are discharged to outdoors.

NOTE: Flue gas may be slightly acidic and may adversely

affect some building materials. If any vent termination is

used and the flue gases may impinge on the building

material, a corrosion-resistant shield (minimum 24 inches

square) must be used to protect the wall surface. If the

optional tee is used, the protective shield is required. The

shield should be constructed using wood, plastic, sheet metal

or other suitable material. All sems, joints, cracks, etc. in

the affected area should be sealed using an appropriate

sealant. See Figure 32.

Intake and exhaust pipes may be routed either horizontally

through and outside wall or vertically through the roof. In

attic or closet installations, vertical termination through the

roof is preferred. Figures 30 through 38 show typical

terminations.

1. Exhaust and intake exits must be in same pressure zone.

Do not exit one through the roof and one on the side.

Also, do not exit the intake on one side and the exhaust

on another side of the house or structure.

2. Intake and exhaust pipes should be placed as close

together as possible at termination end (refer to

illustrations). Maximum separation is 3” (76 mm) on

roof terminations and 6” (152 mm) on sidewall

terminations.

3. On roof terminations, the intake piping should terminate

straight down using two 90° elbows (See Figure 30).

4. Exhaust piping must terminate straight out or up as

shown. A reducer may be required on the exhaust piping

at the point where it exits the structure to improve the

velocity of exhaust away from the intake piping. See

Table 6.

NOTE: Care must be taken to avoid recirculation of exhaust

back into intake pipe.

FIGURE 30

UNCONDITIONED

ATTIC SPACE

1/2" (13mm) FOAM

INSULATION IN

UNCONDITIONED

SPACE

SIZE TERMINATION

PIPE PER TABLE 6.

3"(76mm) MAX.

12" (305mm) ABOVE

AVERAGE SNOW

ACCUMULATION

3" (76mm) OR

2" (51mm) PVC

PROVIDE SUPPORT

FOR INTAKE AND

EXHAUST LINES

8" (203mm) MIN

Inches(mm)

DIRECT VENT ROOF TERMINATION KIT

(15F75 or 44J41)

(IF REQUIRED)

TABLE 6

EXHAUST PIPE TERMINATION SIZE REDUCTION

MODEL

Exhaust Pipe Size

Termination

Pipe Size

*045 and 070

2" (51mm), 2−1/2" (64mm),

3" (76mm)

1−1/2" (38mm)

*090

2" (51mm)

110

2" (51mm)

135

3" (76mm)

2" (51mm)

*−045, −070 and −090 units with the flush mount
termination must use the 1 1/2"accelerator supplied with the
kit.