APC 66123 User Manual

Page 12

Advertising
background image

12 - 3402230800/AC

Configuration of the JBUS/MODBUS communication parameters

◗ Use the cord supplied with the card

◗ Connect the card to a computer

◗ Use a terminal emulator such as HyperTerminal

TM

with these settings

"Echo typed characters locally" option: disabled

◗ Check that UPS power is on.

◗ Type MGEUPS (or mgeups).

The main configuration menu is displayed::

◗ Press the 5 key (Jbus configuration).

The Jbus configuration menu is displayed:

Through settings port

Bits per second

Data bits

Stop bits

Parity

Flow control

9600

8

1

none

none

APC by Schneider Electric
Network Management Card & Modbus/Jbus
Release : AB.build_5_0_7

1 : Reset

2 : Network configuration
3 : Set Login Password to Default

4 : Return to Default Configuration

5 : Jbus configuration
6 : Sensor configuration

0 : Exit

Jbus settings

1 : Display Jbus settings

2 : Modify Jbus settings

3 : Display Jbus diagnostics
4 : Reset Jbus diagnostics

5 : Return to Jbus Default Configuration

6 : Display Jbus frames
0 : Exit

66102

Settings/Sensor

ETHE

RNET

100M 10

M

UPS dat

a RS2

32

On = Lin

k

Blink =

Act

ETHERNET

66103

UPS data R

S232

100M

10M

66103

UPS data

RS232

100M

10M

UPS

Connect the RS232 link to a

terminal

(Microsoft Hyper terminal)

Advertising