The Network Management Card & Modbus/Jbus (66123) can be hot-plugged in MGE

TM

Galaxy

TM

7000

equipped with a Minislot. It is not necessary to shutdown the UPS, disconnect the load or restart the UPS.

◗ Note the MAC address of the card before inserting it.

◗ Insert and secure the card with the screws.

◗ Connect the ETHERNET cable.

◗ Check the ETHERNET port indications.

◗ Wait until the UPS Data LED flashes regularly (approx. two minutes), indicating that card start-up has
terminated correctly.

Note. Connection detection continues until the card has been connected to the network. Once connection is
made, card start-up continues.

Once the card has started, proceed as indicated below.
◗ Connect the serial cable to card’s service port and PC’s COM port

◗ Use a terminal emulator such as HyperTerminal

TM

with these settings

"Echo typed characters locally" option: disabled

◗ Type MGEUPS (or mgeups).
The main configuration menu is displayed:

IP SETTINGS

Bits per second

Data bits

Stop bits

Parity

Flow control

9600

8

1

none

none

APC by Schneider Electric
Network Management Card & Modbus/Jbus
Release : AB.build_5_0_7

1 : Reset

2 : Network configuration

3 : Set Login Password to Default
4 : Return to Default Configuration

5 : Jbus configuration

6 : Sensor configuration
0 : Exit

ETHERNET

UPS

Settings

/Sensor

66103

UPS data

RS232

100M

10M