Installation – Blodgett KLT-G Series User Manual

Page 8

Advertising
background image

6

OM-KLT-G

For efficient performance the kettle must be installed in a well-ventilated area. Items

which might restrict or obstruct the flow of air for combustion and ventilation must be

removed. The area directly around the appliance must be free of combustible materials.

1. Installation can be on a combustible or noncombustible floor. Clearances should

be per table below.

2. The kettle should be installed in an adequately ventilated room with provision

for adequate air supply. The ventilation must employ a vent hood and exhaust

fan with no direct connection between the vent duct and the kettle flue. Do not

obstruct the flue or vent duct after installation.

3. Set the kettle in place and level it using a spirit level on the bar rim, by turning

the bullet or flange feet to adjust leg length. Allow clearance around the unit for

cleaning, maintenance and service.

4. Complete the piping to the gas service main with ½” line or approved equivalent.

5. For standard units, provide 115 vac, 60 Hz, single phase 5 AMP electrical

service. The unit may also be ordered for alternate electric service of 208 VAC or

240 VAC. Observe local codes and/or The National Electrical Code in accordance

with ANSI/NFPA 70 (current edition), or the Canadian Electrical Code, CSA C22.2

(current edition), as applicable. Use the wiring diagram inside the service panel

and at the rear of this manual

6. Bring electrical service through the entrance at the rear of the support housing

with a ½ inch conduit connector. Make a watertight connection with the

incoming lines.

7. Electrically ground the unit at the terminal provided.

8. After the kettle has been connected to the gas supply, check all gas joints for

leaks. DO NOT USE FLAME TO CHECK FOR LEAKS. A thick soap solution or other

suitable leak detector should be employed.

Installation

WARNING

THE UNIT MUST BE INSTALLED BY

PERSONNEL WHO ARE QUALIFIED TO WORK

WITH GAS, ELECTRICITY AND PLUMBING.

IMPROPER INSTALLATION CAN

CAUSE INJURY TO PERSONNEL AND/OR

DAMAGE TO THE EQUIPMENT. THE UNIT

MUST BE INSTALLED IN ACCORDANCE WITH

APPLICABLE CODES. THE UNIT MUST BE

INSTALLED BY A LICENSED PLUMBER

OR GAS FITTER WHEN INSTALLED WITHIN

THE COMMONWEALTH OF MASSACHUSETTS.

DANGER

ELECTRICALLY GROUND THE UNIT AT

THE TERMINAL PROVIDED. FAILURE

TO GROUND UNIT COULD RESULT IN

ELECTROCUTION AND DEATH.

Model

Minimum

Clearance from

Combustible walls

Minimum

Clearance from

Non-Combustible walls

Recommended

Clearances

Left Side

6 in.

0 in.

6 in.

Right Side

6 in.

0 in.

10 in.

Rear

10 in.

10 in.

12 in.

Advertising