Ups shutdown screen – American Power Conversion Bypass Static User Manual

Page 18

Advertising
background image

12

Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

UPS Shutdown screen

The UPS Shutdown screen shows a list of actions, which need to be completed in order to shut down
the UPS. The actions are initially indicated in red to show that they have not yet been completed. A
yellow bar will highlight the actions in the order in which they need to be completed. As actions are
completed they will change to green.

The Start-Up procedure is described in “System Shutdown from Online to Manual
Bypass Operation” .

Normal

Normal

UPS Shutdown

5.40 PM

Initiate transfer to static bypass

Close breaker Q3

Open breaker Q5

Push UPS "OFF" button

Open breaker Q2

Open battery breakers Q7 and Q8

Open breaker Q1

Initiate transfer

Load will be on manual bypass

SSW input

UPS power down

UPS output

Isolate UPS from battery

UPS input

Advertising