Symmetra® MW with Internal Bypass Static Switch - User Guide - 990-1756A-001

47

Appendix A

Air Filter Exchange

Check air filters at regular intervals (every 3 months under normal working conditions) for
accumulated dust on the surface facing the finishing panels. Change all filters at the same time.

Pull lower part of top finishing panel free of the UPS.

Lift finishing panel free of the dead front panel and remove.

Follow this procedure to remove the next finishing panel down, until all panels in one row have
been removed. Use the same procedure for the next row of panels until all panels have been
removed from the UPS system.