Tce installation information – A.J. Antunes & Co TCE 8253420060 User Manual

Page 2

Advertising
background image

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188

TCE Installation Information

1-630-784-1000 Fax: 630-784-1651

Page 2 of 4

P/N 1011092 Rev. A 11/11

1-800-253-2991

Zero

N.C.

C.
N.O.

Span

TC-

TC+

Earth Ground

Power
Input

{

Relay
Output

}

The wiring diagram shows connections for a Type J or K

thermocouple wire via terminals. For a long thermocouple

run, the proper thermocouple extension wire must be

used, and the proper polarity must be maintained. If

these precautions are not observed, the unit may not

meet specifications.

Power and thermocouple wire should not be placed in

the same conduit or wiring trough. However, wires from

several thermocouples may be in the same conduit or

wiring trough.

If shielded thermocouples are used, the shields should

be insulated electrically from the thermocouple wires and

terminated to earth ground.

The unit will read “EEE” for over range conditions, and

“---” for under range conditions.

If field calibration is required, a two-point calibration

with a millivolt generator can be used. Allow 30 minutes

for the unit to stabilize before calibrating. Calibrate the

low reading by adjusting the zero pot. Enter the second

calibration higher than the first point and adjust the span.

Recall these two points if needed.

Wiring Diagram

Wiring for Different Power Requirements

The figure above illustrates how to wire the relays for the

different power requirements. The relay must have an

external power source for you to be able to control your

device.

Unit Power In

Control Device Power In

To Device

Being Controlled

Unit & Control Device

Power In

To Device

Being Controlled

112 VAC/DC

115 VAC

230 VAC

50/60Hz

112 VAC/DC

115 VAC

230 VAC

50/60Hz

Advertising
This manual is related to the following products: