Model A Switches

You are installing one of the finest switches of its type

on the market. The Model A is adjustable within its range

as shown on the range scale located on the front of the

unit. The latch position in the reset models and the level

indicator position in the recycle models show whether the

switch is on or off.

Dimensions

IMPORTANT

Please read these instructions carefully to assure

correct installation. This equipment must be

installed only by a licensed electrician who is

experienced with combustion safeguard control

systems and understands the functions of inter-

locking switches, such as gas pressure switches.

Prior to being put into operation in conjunction

with the combustion safeguard systems, all

switches should be tested for proper range setting

and proper wiring. Check piping connections and

switch house for leaks with a soap bubble test. All

exhaust fans and blowers should be inspected and

checked for proper rotation prior to starting up.

Model A Installation Information

Range Available

4 1/16”

(103 mm) dia.

4 1/16”

(103 mm)

Gas Inlet 1/4” NPT

4 1/16”

(103 mm) dia.

Vent 1/8” NPT

FRONT

SIDE

NOTE: Dimensions

are for reference only.

Single Gas Pressure Switch

High Low Gas Pressure Switch

3/8” NPT

High Pressure

Inlet

5 5/8”

(143 mm)

1/8” NPT

Gas Vent

4 1/4”

(108 mm)

FRONT

SIDE

5 3/8”

(136 mm)

1/8” NPT

Low Pressure

Gas Vent

NOTE: Dimensions

are for reference only.

High Gas Pressure

Low Gas Pressure

2 - 16” W.C.

50-400 mm

1-6” W.C.

25-150 mm

5 - 28” W.C.

125-700 mm

1-35” W.C.

25-875 mm

10 - 50” W.C.

250-1250 mm

2-14” W.C.

50-350 mm

2-20” W.C.

50-500 mm

6-24” W.C.

150-600 mm

10-50” W.C.

250-1250 mm

Specifications

Electrical Ratings: 10A, 1/8 HP @ 125 VAC; 5A, 1/4 HP

@ 250 VAC; Pilot Duty, 125 VA @ 125-250 VAC
Max. Surge Pressure: 10 PSI
Max. Ambient Operating Temperature: 140°F (60°C)
Min. Ambient Operating Temperature: -40°F (-40°C)
Shipping Weight: HGP-A, LGP-A, RHGP-A, RLGP-A:

2 lbs. (.9 kg)

HLGP-A, RHLGP-A: 4 lbs. (1.8 kg)
Options:
Panel Mount
Dust Proof