Model a installation information – A.J. Antunes & Co RLGP-A 803112704 User Manual

Page 2

Advertising
background image

A. J. ANTUNES & CO. www.ajantunes.com 180 Kehoe Blvd., Carol Stream, Illinois 60188

Model A Installation Information

1-630-784-1000 Fax: 630-784-1651

Page 2 of 4

P/N 1011087 06/10

1-800-253-2991

Electrical Wiring-Combination Models

Electrical Wiring-Single Models

Model: HLGP-A

Duty: High Low Gas Reset Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC

5A, 1/4 HP, 250 VAC

Pilot Duty: 125 VA, 125-250 VAC

Indicator On

Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 10 PSIG

Reset lever will latch
when gas pressure is
below setting

High Gas

NO

C

By Others

R e s e t
HLGP-A

Reset lever will latch
when gas pressure is
above setting

Indicator Off

C

Low Gas

NC

By Others

NO

Model: RHLGP-A

Duty: High Low Gas Reset Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC

5A, 1/4 HP, 250 VAC

Pilot Duty: 125 VA, 125-250 VAC

Indicator On

Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 10 PSIG

Contacts C & NC
break when pressure
rises

above setting

High Gas

NO

C

By Others

R e s e t
RHLGP-A

Contacts C & NO
make when pressure
rises

above setting

Indicator Off

C

Low Gas

NC

By Others

NO

Model: HGP-A

Duty: High Gas Reset Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC

5A, 1/4 HP, 250 VAC

Pilot Duty: 125 VA, 125-250 VAC

Indicator On

Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 10 PSIG

Reset lever will latch
when gas pressure is
below setting contact
C & NC make

NC

NO

C

By Others

R e s e t
H G P - A

Model: LGP-A

NC

NO

C

By Others

Reset lever will latch
when gas pressure is
above setting contact
C & NO make

R e s e t
L G P - A

Duty: Low Gas Reset Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC

5A, 1/4 HP, 250 VAC

Pilot Duty: 125 VA, 125-250 VAC

Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 10 PSIG

Indicator Off

Model: RHGP-A

Duty: High Gas Recycle Switch
Elec. Rating: 10A, 1/8 HP, 125 VAC

5A, 1/4 HP, 250 VAC

Pilot Duty: 125 VA, 125-250 VAC

Indicator On

Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 10 PSIG

Contacts C & NC
break when pressure
rises above setting

NC

NO

C

By Others

Recycle
RHGP-A

Model: RLGP-H

NC

NO

C

By Others

Contacts C & NO
make when pressure
rises above setting

Recycle
RLGP-A

Duty: Low Gas Recycle Switch
Elec. Rating: 10A: 1/8 HP, 125 VAC

5A, 1/4 HP, 250 VAC

Pilot Duty: 125 VA, 125-250 VAC

Field wiring to be rated @75ºC for max 120ºF Ambient
Field wiring to be rated @90ºC for max 140ºF Ambient
Max Surge Pressure: 10 PSIG

Indicator Off

Advertising