JD-2 Installation Information

1-630-784-1000 Fax: 630-784-1651

Page 2 of 4

P/N 1011082 06/10

1-800-253-2991

Air Connections

Tubing recommended as minimums: 1/4” copper or alu-

minum tubing, or 1/8” pipe. All tubing and pipe must be

clean and free from oil, dirt, and chips. If piping runs over

five feet long, use a larger size tubing or pipe, and reduce

size at switch.

Air Supply

The switch is equipped with two 1/8” NPT connection

ports. Connect air supply as shown below. When used for

vacuum or pressure applications, the JD-2 must always

be vented as shown. No venting is required for differential

applications.

Differential Inlet Connection

Vacuum Only Inlet Connection

Terminal Connections

Conduit Connection

Pressure Only Inlet Connection

IN

W.C.

4

3

2

1

.5

.1

ING

Low Vacuum or

Low Pressure

High Vacuum or

High Pressure

IN

W.C.

4

3

2

1

.5

.1

ING

Vacuum Connection

top chamber

Vent Leave

Open

IN

W.C.

4

3

2

1

.5

.1

ING

Pressure Connection

Bottom Chamber

Vent Leave

Open

Indicator Position

Terminal

Off

C and NO open
C and NC closed

On

C and NO closed
C and NC open

C

NO

NC

Hole for 7/8” Conduit Connection