AIR PURGE AND TEST OPERATION

1) Air Purge

Choose Purge method from the table.

Connective Pipe Length

Air Purging Method

Additional amount of

refrigerant to be charged

less than 16.4 feet

Use vacuum pump

N/A

16.4 ~ 32.8 feet

Use vacuum pump

0.32 ounces per foot for each foot

beyond 16.4 feet (5 meters).

Make sure the R410A refrigerant added into air conditioner is liquid form.

When relocating the unit to another place, perform evacuation, with a
vacuum pump.

CAUTION IN HANDLING THE PACKED vALvE

Open the valve stem until it hits against the stopper. Do not try to open it further.

Securely tighten the valve stem cap with a spanner or the like.

Valve stem cap tightening torque.

Liquid pipe side

O 1/4”

11.57 ft lbs

(160kgf.cm

Gas pipe side

O 3/8”

21.7 ft lbs

(300kgf.cm)

Refrigerant Gas

Packed Valve

c

ondensor

(o

utdoor

)

u

nit

e

vaporator

(i

ndoor

) u

nit

B

A

Half union

Packed valve

Valve stem

Flare nut

Stopper

Cap

O 0.5 inches (>10000Btu/h)
O 0.38 inches (<9000Btu/h)

O 0.25 inches