Panasonic S25FM3HPQ User Manual

Page 7

Advertising
background image

S-20~125FM3HPQ
Urban Multi air conditioner
4PW15114-1A

Installation and operation manual

5

When electric wiring work is finished

Check drainage flow during COOL running, explained in "Test operation"
on page 7.

When electric wiring work is not finished

Remove the switch box cover and connect the single-phase power
supply and the remote controller to the terminals. (Refer to "Electric
wiring work" on page 5 for switch box attachment/detachment.)
(Refer to figure 11a and figure 11b)

Next, press the inspection/test operation button

on the remote

controller. The unit will engage the test operation mode. Press the

operation mode selector button

until selecting fan operation

. Then, press the on/off button

. The indoor unit fan and drain

pump will start up. Check that the water has drained from the unit.

Press

to go back to the first mode.

E

LECTRIC

WIRING

WORK

General instructions

All field supplied parts and materials and electric works must
conform to local codes.

Use copper wire only.

Follow the "Wiring diagram" attached to the switch box cover to
wire the outdoor unit, indoor units and the remote controller. For
details on hooking up the remote controller, refer to the
"Installation manual of the remote controller".

All wiring must be performed by an authorized electrician.

A circuit breaker capable of shutting down power supply to the
entire system must be installed.

This system consists of multiple indoor units. Mark each indoor
unit as unit A, unit B..., and be sure the terminal board wiring to
the outdoor unit and HR box are properly matched. If wiring and
piping between the outdoor unit and an indoor unit are
mismatched, the system may cause a malfunction.

Electrical characteristics

MCA: Min. circuit Amps (A)

MFA: Max. Fuse Amps (A)

KW: Fan Motor Rated Output (kW)

FLA: Full Load Amps (A)

Specifications for field supplied fuses and wire

Allowable length of transmission wiring between indoor and outdoor
units, and between the indoor unit and the remote controller is as
follows:

1.

Outdoor unit - indoor unit: max. 1000 m (total wiring length: 2000 m)

2.

Indoor unit - remote controller: max 500 m

Caution for drain socket

Do not remove the drain pipe plug. Water might leak out.

The drain outlet is only used to discharge water if the drain
pump is not used or before maintenance. Gently put in and
out the drain plug. Excessive force may deform the drain
socket of the drain pan.

Pulling out the plug

Do not wiggle the plug up and down

Pushing in the plug

Set the plug and push it by using a Philips screwdriver

1

Switch box cover

2

Power supply wiring port

3

Transmission wiring port

4

Wiring diagram

5

Switch box

6

Plastic clamp

7

Remote controller wiring

8

Terminal board for unit transmission wiring

9

Power supply wiring

10

Indoor PC board

11

Power supply terminal board

12

Earth screw

13

Transmission wiring between units

14

Adaptor for PC board

1

1

Drain plug

1

2

1

Drain plug

2

Philips screwdriver

TEST

TEST

Model

Hz

Volts

Voltage range

S-20~125FM3HPQ

50

230

min. 198-max. 264

power supply

Fan motor

Model

MCA

MFA

KW

FLA

S-20•25•32FM3HPQ

0.5

16 A

0.05

0.4

S-40FM3HPQ

0.6

16 A

0.065

0.5

S-50FM3HPQ

0.9

16 A

0.085

0.7

S-63FM3HPQ

1.1

16 A

0.125

0.9

S-80FM3HPQ

1.3

16 A

0.135

1.0

S-100FM3HPQ

1.5

16 A

0.135

1.2

S-125FM3HPQ

2.0

16 A

0.225

1.6

NOTE

For details, refer to "Electrical data".

Power supply wiring

Model

Field fuses

Wire

Size

S-20~125FM3HPQ

16 A

H05VV-U3G

Local codes

Model

Wire

Size

S-20~125FM3HPQ

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to "Wiring example" on page 6.