Stove installation, Alcove installation requirements – Avalon Stoves Rainier User Manual

Page 12

Advertising
background image

12

Stove Installation

(for qualified installers only)

Travis Industries

100-01140

4 020628

Alcove Installation Requirements

Whenever the stove is placed in a location where the ceiling height is less than 7' tall, it is considered
an alcove installation. Because of the reduced height, the special installation requirements listed
below must be met.

•

Chimney connector and chimney must be one of the following types:

• DURAVENT model DVL with DURATEC chimney
• DURAVENT model DVL with DURA-PLUS chimney
• AMERI-TEC model DCC with model HS chimney
• SECURITY model DL with SECURITY model ASHT or S2100 chimney
• METAL-FAB model DW with TG chimney

• GSW Double Wall Chimney Connector with Super Chimney Twenty-One
• SELKIRK METALBESTOS model DS connector with model SSII chimney
• I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
• Standard Masonry Chimney with any one of the above listed connectors

Rainier-45°

Rainier-90°

Minimum Clearance
(See the illustration below)

Combustible

Alcove

Non-Combustible

Alcove

Combustible

Alcove

Non-Combustible

Alcove

A

Sidewall to stove

16"

6"

14"

6"

B

Backwall to stove

14"

4"

9 1/2"

2"

D

Connector to sidewall

25 1/2"

15 1/2"

23 1/2"

15 1/2"

E

Connector to backwall

10"

2"

10 1/4"

2 3/4"

G

Maximum depth of alcove

48"

48"

48"

48"

H

Minimum width of alcove

57 3/4"

37 3/4"

53 3/4"

37 3/4"

J

Minimum height of alcove

84"

6" above stove top

84"

6" above stove top

•

Alcoves are classified as combustible or non-combustible. Non-combustible alcoves must have
walls and a ceiling that are 3 1/2" thick of a non-combustible material (brick, stone, or concrete).
This non-combustible material must be spaced and ventilated at least 1" off of all combustible
materials (walls, ceiling, etc.) to allow air to move around the non-combustible walls and ceiling.
All other alcoves are considered combustible. The clearances below must be met:

Non-combustible alcove
construction (on walls
and ceiling) - see the
explanation above.

3 1/2" thick non-
combustible
material

Combustible

materials

1" Min.

Ventilated
air space

Non-combustible
reinforcer

a

b

d

e

h

j

g