Wiring installation, Wiring diagrams, Electrical shock & fire hazard – COOK Gemini User Manual

Page 3

Advertising
background image

3

unit 3/8”. If filter and deluxe aluminum grille are

both present, raise unit 7/8”, due to the 1/2” grate

protrusion on the aluminum grille. If filter is not

present: the grate on the aluminum grille will fit inside

of the unit (except sizes 160 & 180). Other grilles have

no protrusion and fit flush with the fan.

3. Fasten duct work to the outside of the duct collar

(damper frame) using sheet metal screws and foil

tape. Make sure sheet metal screws are placed

where they do not interfere with damper operation.

4. Fasten the housing to the bottom of the joists

through the holes provided in the mounting bracket.

For Ceiling Radiation Damper Installation

see separate document “Gemini/CRD

Installation Supplement.”

Mounting

Bracket

Filter (optional)

Ceiling

Grille

Joists

Unit Housing

Grate Protrusion

(aluminum grille only)

45

O

Cooking

Equipment

Floor

45

O

Wiring Installation

All wiring should be in accordance with local

ordinances and the National Electrical Code, NFPA 70.

Ensure the power supply (voltage, frequency, and current

carrying capacity of wires) is in accordance with the

motor nameplate. Refer to Wiring Diagrams.

Lock out all power sources before unit is wired to power

source.

Follow the wiring diagram in the disconnect switch and

the wiring diagram provided with the motor. Correctly

label the circuit on the main power box and always

identify a closed switch to promote safety (i.e., red tape

over a closed switch).

Note: Insulate Unused Leads. Fan plug box is designed

for single speed operation, using an FSC to vary speed if

required. Do not wire to more than two leads.

Wiring Diagrams

Gemini 100 Series:

Cap off wire that is not in use.

Ground Screw for

Field Grounding

Green Wire

(Ground by COOK)

Black Wire (High Speed)

Red Wire (Low Speed)

White Wire

(Common)

For fan power supply connection use 4-wire cable

provided in field wiring box shown above. Connect field

ground wire to green ground screw located inside fan

electrical box. Connect one supply line to white wire.

Depending on fan speed requirements connect other

supply line to Red wire for Low Speed or Black wire

for High Speed. Insulate unused Red or Black wire.

Replace electrical box cover. Model 126, 146, 166, 186

are Low Speed. Models 128, 148, 168, 188 are High

Speed.

Gemini 200, 300, 500, 600 and 700 Series:

White

Line

Line

Black (High)

Red (Low)

Electrical Shock & Fire Hazard:

Insulate Unused Lead
Failure to follow these instructions could result in

death or serious injury.

Gemini 400 Series:

White

Line

Black

Line

Wiring continued on the next page.

Notice! Do not install above or around

cooking equipment (shaded area)

Figure 2