Pitco Frialator Multilane Three Basket Fryer Control User Manual
Page 7

Programming Pitco P/N 60126805
Two and Three Basket Controller
7
L20-403 Rev 0 07/12
Single 3 Zone setting is for a 3 Basket fryer with a single product (typically FRIES).
Single 2 Zone setting is for a 2 Basket Fryer with a single product (typically FRIES).
Overlays are available tailored for each of the control TYPE settings.
4
Other Displays:
[PROBE OP] [OPEN]
Open probe detection is standard on all Pitco controls. If probe is detected open, normal heating and
cooking activities are suspended.
[HIGH TMP] [HIGH TMP]
This display warns operators that the vat temperature has exceeded set temperature by 40°F (22°C), or an
absolute maximum of 410°F (210°C). This display does not show the status of the mechanical high limit
switch.
[DRAINING] [TURN OFF]
This message indicates that the drain valve has been opened, the vat is assumed to be empty by the
controller. Normal heat control activities are suspended. To restore to normal operation, close the drain
valve. Display will show [TURN OFF] [TURN OFF]. Turn controller off, and refill the vat. Continue
with normal operations at section 1.
[HEAT] [FAILURE] OR [IGNITION] [FAILURE]
This message indicates that the heating system failed to respond. Typically, the high temperature limit
switch has tripped and is in need of resetting. In the case on gas fired appliances, this message will
display if the pilot fails to light or is detected marginal by the ignition module.
[SYSTEM] [FAILURE]
This message indicates a shorted probe. If probe is detected as a short circuit, normal heating and cooking
activities are suspended.