Low voltage, Power up and test, Document wiring – Pathway DMX Relay Cabinets User Manual

Page 3: 3figure 1 – typical wiring — low-voltage switches, Push-on terminals and wire ties

Advertising
background image

3

Figure 1 – Typical Wiring — Low-Voltage Switches

24V

24V RECT

WHITE

ACCESSORY

POWER SUPPLY

RED

BLACK YELLOW WHITE

2

RED

BLACK

YELLOW

WHITE

1

#20/3 AWG
1600 FEET MAXIMUM DISTANCE
HSSW3 (standard class)
HSSW3P (plenum applications)

RED

BLACK YELLOW WHITE

2

RED

BLACK

YELLOW

WHITE

1

#20/4 AWG
1600 FEET MAXIMUM DISTANCE
HPSW4 (standard class)
HPSW4P (plenum applications)

RED

BLACK YELLOW WHITE

2

RED

BLACK

YELLOW

WHITE

1

#20/4 AWG
1600 FEET MAXIMUM DISTANCE
HPSW4 (standard class)
HPSW4P (plenum applications)

RED

BLACK

YELLOW

WHITE

2

RED

BLACK

YELLOW

WHITE

1

#20/4 AWG
MAXIMUM DISTANCE (See below)

RED

BLACK

YELLOW

WHITE

3

RED

BLACK YELLOW WHITE

2

RED

BLACK

YELLOW

WHITE

1

#20/4 AWG
1600 FEET MAXIMUM DISTANCE
HOSW4 (standard class)
HOSW4P (plenum applications)

STANDARD SWITCH

LOCATION SWITCH

SINGLE SWITCH WITH
PILOT INDICATION

MULTIPLE SWITCHES
CONTROLLING
SINGLE RELAY

SINGLE (OR MULTIPLE)
SWITCH CONTROL
OF A GROUP

(BLUE)

FOR MORE THAN
TWO SWITCHES,
SPLICE CONTROL
LEADS

FOR MASTER PLATE,

USE HMSW25(P)

NUMBER
RELAYS
PARALLEL
2
4
6
8
10

MAXIMUM
DISTANCE
WITH #20/4
750 FEET
325 FEET
180 FEET
110 FEET
65 FEET

MAXIMUM
DISTANCE
WITH #16/4
1900 FEET
825 FEET
450 FEET
275 FEET
160 FEET

Note: Relays 1, 2 and 3
are now permanently
wired as a group.
You can’t control them
individually.
If the pilot contacts are
wired in parallel as above,
turning ON any relay in
the group will cause the
pilot to light.

Test relays by touching each red and black switch

input terminal with a jumper connected to any white

terminal in the panel.

HINxxy12BC/24BC/48BC

Lighting Control Panel Interior — Installation and Setup

Wiring

Line voltage

Before making connections to the
relays make sure that none of the
load circuits are shorted or miswired.

Connect the lighting circuits to the relay
SPST output terminals. Wire the power
supply, following the instructions which
accompany the unit. Connect the ground
wire to the stud provided in the tub.

Low voltage

Wire switches as shown in Figure 1. Wire
sensors and other low-voltage control
devices as shown in the installation
instructions accompanying the devices.
Use

3

16

" push-on terminals and wire ties.

Power Up and Test

Apply power to the power supply only

Using a low-voltage jumper attached to
any WHITE terminal, touch all of the
switch input RED terminals, and then
repeat for the BLACK terminals. The
relays should click on, then off. Confirm
by measuring the line-voltage termina-
tions of the relay. Test the operation of
each low-voltage switch, sensor and
other control device according to the
individual installation instructions.

Document Wiring

Record the circuits controlled by each
relay on the Relay Schedule card
provided with these instructions and then
place it in the plastic sleeve attached to
the inside of the panel cover.