Troubleshooting

If no relays respond to switches …

Check the power supply LEDs. If they
are off, check:

1. the power supply plug-in connection to

the motherboard terminal J1

2. the power feed circuit to the power

supply

If they are still off …

Replace the power supply.

If an individual relay does not
respond …

Remove the switch connections and
check the relay operation directly with a
jumper.

If it still does not work …

Turn off all power to the panel and
replace the defective relay.

Check power supply LEDs. Both should be on.

Test the relay. If defective, replace.

Relay Output Ratings

Both General Electric* RR7P/RR9P and
Reliant Relay* H2R7P/H2R9P relays
may be installed in The Watt Stopper
interiors, including those listed herein.

The GE R7P/RR9P relay output power
contacts are rated as follows:

20A

Tungsten, 125VAC

20A

Ballast, 277VAC

20A

Resistive, 277VAC

1

2

HP @ 110-125VAC

1

1

2

HP @ 220-277VAC

The Reliant Relay H2R7P/H2R9P relay
output contacts are rated as follows:

20A

Tungsten

20A

Ballast

20A

General use

1HP

@ 120VAC, 50-60Hz

Compatibility with GE Total Lighting
Control enclosures

All Watt Stopper interiors are fully
compatible with respective GE tubs,
covers and power supplies as defined in
the table below. All Watt Stopper
warranties apply whether the interior is
used in a Watt Stopper or General
Electric enclosure.

The Watt

Compatible

Compatible

Stopper

GE Tub/Cover

GE Power

Cat.#

Cat.#

Supply Cat.#

HINxxy12BC

RTUB12/RCOV12xx

RPWRxxx

HINxxy24BC

RTUB24/RCOV24xx

RPWRxxx

HINxxy48BC

RTUB48/RCOV48xx

RPWRxxx

In Watt Stopper interiors, the xx stands for the number of
installed relays and the y indicates the type: G for General
Electric or R for Reliant Relay.

* All trademarks are the property of the respective parties.

HINxxy12BC/24BC/48BC

Lighting Control Panel Interior — Installation and Setup

Note: The view shown above is of a Complete

Control lighting panel interior. It is representative of

Basic Control troubleshooting.

Advertising