Setup/configuration file – Bell & Gossett 10-001-275 XLS Integrated Pump Controller User Manual
Page 30

30
Typical BacNet communications settings are as
follows:
Page BacNet - Link
Serial Encapsulation
TCP/IP
Link Type
BacNet IP
Device UDP Port
47808
MSTP MAC
Page
BacNet - Modem
Configuration
Modem Identifier
Auto Detect 2
Phone Number
<As
Required>
Page BacNet - Modem Options
Enable incoming calls
No
Auto Connect Enable
Yes
Auto Connect Retry
Interval (s)
120
Disconnect if call idle
more than...
1
Auto-Disconnect time (s)
120
Page BacNet - Com Port
Com Port
COM2
Baud
9600
Data Bits
8
Stop Bits
1
Parity
None
Page BacNet - TCP and UDP
IP Address
192.168.1.15
Port #
47808
Server Mode
Yes
Page BacNet - Advanced - A
Protocol-Station
1
Protocol-Retries
0
TX Buffer
512
RX Buffer
512
Page BacNet - Advanced - B
TimeOut-Start
1000
TimeOut-End
0
TimeOut-Interval Between
Char
500
TimeOut-Wait CTS
100
Page BacNet - Advanced - C
Control RTS
No
Verify CTS
No
Disable DTR
No
Enable IR
No
Table 2: BacNet Settings
Setup/Configuration File
ActiveX and IP Updates
Tap [ActiveX and IP Updates] from the Options
Setup Menu.
By default both ISSymbol URL and Agent URL are
automatically populated.
View Current Configuration: View the entire URL
in a popover screen.
Set Configuration: Set and save new web
configurations.
Email: Get notifications via email.
Tap [Close] to return to the Options Setup Menu.
Figure 72: ActiveX and IP Updates
WinCE Remote Access
Tap [WinCE Remote Access] from the Options
Setup Menu
This screen allows you to communicate with a remote
server using Telnet. This feature is intended for
advanced custom jobs.
CAUTION:
Before using this feature or changing any settings
on this screen, please call customer service.
Tap [Close] to return to the Options Setup Menu.