Comfort-Aire VFH 24 CA User Manual

Page 6

Advertising
background image

VFH InverterFlex

®

- Ceiling Cassette

Heat Controller

9.

Installation is designed for new or existing ceilings. However, anchoring/mounting to wood, steel, and

concrete must follow all local/national building codes.

10.

Mounting hardware for suspension in ceiling must be acquired locally. M10 or 3/8” diameter threaded

rods and nuts are the recommended to ensure a proper fit with the mounting flanges of the unit.

Location Considerations:

The location must take into consideration the size of the indoor unit, ceiling opening, and where the threaded

rods must be located to suspend the unit:

Model

Capacity

Ceiling Opening Dimensions

Unit Dimensions

Threaded Rod Dimensions

A x A in(mm)

B x B in(mm)

C1 x C2 in(mm)

12/18K

25.6(650) x 25.6(650)

22.4(570) x 22.4 (570)

15.8(400) x 23.8(604)

24K

35.0(890) x 35.0(890)

33.1(840) x 33.1(840)

26.8(680) x 30.7(780)

12/18K Model Dimensions:

24K Model Dimensions:

Additional considerations:

Allow at least 6.3in (160mm) clearance from the top of the installation flange of the unit and the top of

the ceiling cassette panel.

The drop ceiling tile should overlap the edge of the ceiling cassette panel by at least 0.8in (20mm).

4

A

B

C1

A

C2

B

A

C2

B

A

B

C1

0.8 in. (20 mm)

6.3 in.

(160

mm)

Advertising