Line Set Installation

ATTENTION: Refer to the Outdoor unit’s installation manual for all line set sizes and charging information.

Create Opening for Refrigerant and Condensate lines

1.

Determine hole position according the unit’s required clearances and which direction the lines will be

routed from your unit.

2.

Drill a 2.5”(65mm) hole angled downward (approx. 45°) toward the outdoors, if the line sets are being

routed through a side wall.

WARNING: Ensure that neither studs nor plumbing are located directly behind the proposed opening

location.

3.

Always use a conduit to route the piping though the hole in the wall.

4.

Properly seal the hole after routing the pipes through to prevent debris, insects, or small animals from

entering.

Line Set Connection

When connecting the line set to the unit, use two wrenches – one to hold the flare connection on the unit and

the other to attach and tighten the flare nut of the line set.

Attention: The 24K indoor unit comes with a connecting pipe to help provide some flexibility between the rigid

connections (unit connection and the line set). This helps prevent the line from being kinked and allows for a

proper bend radius. The connecting pipe has a flare connection to attach to the unit’s refrigerant connector and

a straight piece of copper on the other end, which would need to be flared and brazed in order to connect to the

end of the line set from the outdoor section.