Installation Instructions
ASSA ABLOY’s standard-based Hi-O system—
Highly Intelligent Opening—connects electronic
(Controller Area Network) data network,
allowing them to communicate and monitor the
health of the opening. Intelligence is built into
each device instead of one centralized logic
unit, creating a plug-and-play system. Each
device is instantly recognized when plugged
into the system—similar to what happens when
a USB device is plugged into a computer.
Every unit is connected with a four-wire cable
and has ElectroLynx® plug-in connectors for
quick installation.
Hi-O is based on devices with built-in
intelligence and a CANbus that links all the
devices together. Data traffic on the Hi-O
CANbus can be encrypted. Each Hi-O device
(such as a push plate, electric strike, card
reader, door operator, etc.) is connected to the
CANbus through a single, four-wire cable. Two
of the wires supply power and the other two
are used for data communication.
Refer to the Hi-O Systems Manual (A8002).
Hi-O Overview
2. For available faceplate options, see page 8.
Prepare Strike
Prepare Frame
1. Evaluate opening and reset Dip Switch if needed (see
page 4 (ADJUSTMENT INSTRUCTIONS).
1. Prepare frame using the appropriate template for your
lockset and faceplate combination (see page 3-4).
2. Connect to system using electrolynx connectors (see Page
3).
Diagram A
3. Install the HT5000 strike body into the door frame.
4. Set up the Hi-O system (see pages 5-7.
Installation Instructions
3
The HT5000 series drawing
below show the Hi
-
O application
.
Voltage: 12-24VDC
(11-28VDC range) operation
Filtered and Regulated Power Supply
Current: .
5 Amp Seated
.04 Amp Unseated
PIN 1 Black (0 VDC)
PIN 3 White (CANbus)
PIN 5
PIN 7 Brown (CANbus)
PIN 8
PIN 6
PIN 4
PIN 2 Red (+12 – 24 VDC)
-)]
NOTE:
For HT5000 (On the 8-Pin Connector):
PIN 2 Red (Power +12 - 24VDC)
PIN 1 Black [Power 0 VDC/Common(-)]
PIN 3 White CAN bus HIGH
PIN 7 Brown CAN bus LOW
endly with quick
cable lengths to a minimum.
.
The System is designed to be installation friendly with quick
connectors.
The total length of the bus should not be more then 50 meters
(164 feet) and stub (star) connections should not be more then
10 meters (33 feet). The optimal solution places the door
controller close to the door to keep cable lengths to a minimum.
IMPORTANT:
ElectroLynx connectors plug and lock together in only one way,
as shown.
Do NOT force connectors together.
Prepare Strike
Wiring
A. Electrolynx Connectors
B. Electrolynx Connector System Notes