Kramer Electronics TP-185 User Manual
Page 12

Connecting and Configuring the TP-185
9
9
6.4 Connecting Multiple TP-185 Units via the RS-485 Bus
You can connect up to 8 TP-185 units via the RS-485 bus with control from a PC or
serial controller.
To connect up to 8 TP-185 units via RS-485 (see
1. Connect the RS-485 terminal block of the first TP-185 to the RS-485 terminal
block of the second TP-185, and so on (see
Section 6.3
2. Set each TP-185 Machine number to be a unique number (see
), connecting all the
TP-185 units via the RS-485 terminal blocks.
Section 7.1.3
3. On the first and last TP-185 physical devices on the RS-485 bus, set the
RS-485 TERM DIP-switch ON (terminating the RS-485 line at 120
Ω, see
Section 7.1.1
4. On all other TP-185 units, ensure that the RS-485 Term DIP-switch is OFF.
).
Figure 3: Connecting Multiple TP-185 Units via RS-485