Typical wiring diagram, Locating system distance – Light Engineered Displays Linear Detection with Footage Marks User Manual
Page 2

DL
SERIES
LOCATING SYSTEM
DISTANCE
4“ SQUARE BOX
Main input power must be from appropriate
disconnect device, as per code require-
ments.
Wiring must be routed and supported in
manner that prevents strain or damage to
wire and connectors.
Conduit provides grounding.
1.
2.
3.
Typical Wiring Diagram
LCD-240
LD-2000
1 2 3 4 5
Pwr
Data
+
-
RX +
RX -
Pwr
+ -
W BG R
To Water Leak Sensing Cable
Power Supply
Display on Door
Controller in Backbox
A B S
+ -
n/c
n/c
120 vac input
24 vdc output
H
N CAUTION
120 VAC
Rear View
NO C NC
Contacts
END OF LINE DEVICE
18 Gauge THHN
four-conductor cable
with jacket. Install
per local codes.
CONDUIT
STARTER CABLE
DLC-100
DLC-50
STRAINRELIEF
WITH RUBBER BUSHING
CONNECTORS
NOTE: CABLE LENGTH SHOULD BE LIMITED
TO 1400 FEET PER ZONE, MAXIMUM.
NOTE: If the start of the DLC-100 cable is
within 10’ of the controller, the starter
cable can be connected directly to the
controller.
TO CONTROLLER