tension is needed to prevent the damper plate

from rattling when closed. Mount the Lintel

Hook to the masonry with the screws provided.

4. Attach Chimney: Attach the first Chimney

Section onto the Anchor Plate by using the

sheet metal screws provided. Always maintain

at least a 2-inch clearance to combustibles.

The 2-inch clearance is an air space; do not

fill that clearance space with any materials. If

an offset is required, refer to the Elbow Offset

Installation Section below.

5. Frame Openings: From the ceiling, drop a

plumb bob to the center of the fireplace’s flue

outlet and mark this center point on the ceiling.

Refer to Table 1 for the framing dimensions.

Mark appropriate cutting lines around the

center point. Cut a square hole in the ceiling.

Frame a level, square opening centered over

the hole that you have cut. Frame openings at

each floor level above the Fireplace (Fig. 4).

These openings are to hold the Firestop and

Attic Insulation Shield. Locate each opening by

dropping a plumb bob to the four corners of the

opening below. Maintain the minimum 2-inch

clearance/air-space.

6. Cut Roof Opening: If penetrating through

the roof, determine and cut an opening in the

roof directly above the opening below. The

cut opening must be at least 4-inches larger

than the chimney’s outside diameter to provide

at least a 2-inch clearance all around the

chimney. The chimney must be centered within

this opening and maintain the minimum 2-inch

clearance to combustibles.

7. Install Firestop: A Firestop is required on

each floor penetration in multistory installations.

Building Codes require a Firestop at every

floor/ceiling level, including where the chimney

penetrates into the attic. Figure 4 shows a

typical 2-story installation with an attic. Note:

a Firestop is not installed where the chimney

penetrates through the roof. The Firestop is

FRAMING

Figure 5

Figure 6

Figure 7

SECURE BRACKET TO FRAME

SUPPORT UP TO

25 FEET OF CHIMNEY

MAINTAIN 2" CLEARANCE

EACH SUPPLEMENTARY

INSTALL SUPP. SUPPORT

IF HEIGHT EXCEEDS 50’

OR IF REQUIRED BY THE

FIREPLACE MANUFACTURE

FROM CHIMNEY TO FRAMING