DuraVent DuraStack Installation User Manual

Installation instructions, Models dis / das, Warnings

Advertising
background image

PIDIS REV.

2 04/2013

Listed to standards:
UL 103 and ULC S604
UL-1978 (DIS only)
ULC/ORD
-C959 540°C and 760°C
Report # 3162834

WARNINGS

FAILURE TO FOLLOW THESE INSTALLATION

INSTRUCTIONS COULD CAUSE FIRE, CARBON

MONOXIDE POISONING, OR DEATH. IF YOU ARE

UNSURE OF INSTALLATION REQUIREMENTS, CALL

THE PHONE NUMBER LISTED ON THE BACK OF

THESE INSTRUCTIONS.

A MAJOR CAUSE OF CHIMNEY RELATED FIRE IS

FAILURE TO MAINTAIN REQUIRED CLEARANCES

(AIR SPACES) TO COMBUSTIBLE MATERIALS. IT

IS OF UTMOST IMPORTANCE THAT THIS CHIMNEY

BE INSTALLED ONLY IN ACCORDANCE WITH THESE

INSTRUCTIONS.

Double Wall Construction Positive Pressure Chimney Systems

MODELS DIS / DAS

Boiler and Engine Exhaust Chimney Systems

Grease Duct Systems

(DIS only)

INSTALLATION

INSTRUCTIONS

This installation manual will enable you to obtain a safe, efficient and

dependable installation of this positive pressure chimney system.

Please read and understand these instructions before beginning your

installation.

Do not alter or modify the components of this chimney system under any

circumstances. Any modification or alteration of the chimney system

or approved accessories, including but not limited to the appliance

it is connected to, may void the warranty, listings and approvals of

this system and could result in an unsafe and potentially dangerous

installation.

SUITABLE FOR POSITIVE PRESSURE VENTING APPLICATIONS WITH

MAXIMUM 60” WATER COLUMN INTERNAL STATIC PRESSURE AT

1000 DEGREES F.

SAVE THESE INSTRUCTIONS

FOR FUTURE REFERENCE

DIS: INSULATED
DAS: UNINSULATED