ROOF BRACE (RB)

1...The.roof.brace.is.used.to.stabilize.the.chimney.where.it.extends.more.

than.15’.above.the.roof.

2...It.consists.of.one.band.(RB).and.two.braces.(supplied.by.the.installer).

3...To.minimize.loads.induced.by.thermal.expansion.on.braces.and.sup-

port,.the.maximum.distance.between.the.last.fixed.support.and.the.

band.of.the.roof.brace.must.be.reduced.to.5’.

4...Begin.by.attaching.the.braces.to.the.band.with.supplied.bolts.and.

nuts...Next,.install.the.band.on.the.chimney.and.tighten.the.band...Fix.

the.braces.to.the.roof.at.120°...Make.sure.you.have.a.rigid.structure.

on.the.roof.

Figure 34 - Roof brace assembly

GUY WIRE (GW)

1...The.guy.wire.is.used.where.the.chimney.extends.more.than.15’.above.

the.roof.

2...It.consists.of.a.band.designed.to.receive.3.guy.wire.(supplied.by.others).

at.120°.apart.or.6.guy.wire.at.60°.apart.for.diameter.larger.than.24”..

The.guy.wires.are.fixed.to.the.roof.by.mean.of.tensioner.and.anchor.

(also.by.others).

3...When.installing.guy.wire,.the.cable.must.be.slightly.slack.or.loose.to.

allow.thermal.expansion.or.be.equipped.with.tensioning.springs.(by.

others)...The.tensioning.springs.are.mandatory.only.when.there.is.

more.than.one.level.of.guy.wire.needed.

4.. To.minimize.the.effect.of.thermal.expansion,.good.practice.implies.

installing.a.fixed.support.and.an.expansion.length.at.the.roof.level.

(see.Figure 35.’guy.wire’).

Figure 35 - Guy Wire

1-1/4” Rigid galvalume tube

or 1-1/2” x 3/16” angle iron

(by others)

Fixed support

5’ Max

H

120°

Guy Cable * tensioners and

roof anchors * (by others)

Guy wire band (GW)

Fixed support

H

Expansion length

* Cables and roof anchors

designed for 30 lb. per

sq. ft. force on chimney

projected area.