Standard tee with dam

POSITION #2

(T90D2)

NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

27

GREASE TEE 90° (GT90P) / TEE 90 DAM (T90D) (DIS ONLY)

The.Grease.Tee.90.and.the.standard.Tee.90.with.a.dam.are.used.to.pro-

vide.access.for.clean-out.to.comply.with.NFPA.96.requirements..They.

are.equipped.with.a.1-1⁄2”.(38).high.grease.dam.at.the.access.port..

The.access.port.must.be.closed.with.a.tee.cap.(TC)..The.location.of.the.

access.port.in.the.tee.is.dependent.on.the.orientation.of.the.tee.in.the.

final.installation..Access.port.location.is.coded.as.shown.in.Figure 71.

Figure 71 - Grease tees

Figure 72 - Grease tee Y

Male coupling

Grease dam

Grease tee

POSITION #1

(GT90P1)

Male coupling

Grease dam

POSITION #1

Male coupling

Grease tee

POSITION #2

(GT90P2)

Grease dam

POSITION #2

Male coupling

Grease dam

POSITION #3

Grease tee

POSITION #3

(GT90P3)

Male coupling

Grease dam

Standard tee with dam

POSITION #1

(T90D1)

GREASE TEE Y (DIS ONLY)

1....The.Grease.Tee.Y.(GTY).is.very.useful.where.the.grease.duct.must.

be.accessed.for.clean-out.and.inspection.purposes...See.Figure 72.

2....It.can.be.used.in.place.of.the.Grease.Tee.90.(GT90).and.provides.

excellent.access.clearance.for.clean-outs.

3....Clean-outs.must.be.located.at.all.direction.changes.in.the.grease.

ductwork.

4....Installation.is.the.same.as.standard.tee.