SECTION D - ROOF AND WALL PENETRATIONS

ROOF/FLOOR PENETRATION

1.. The.roof/floor.penetration.consist.of.a.firestop.radiant.shield.(FS),.a.

flashing.(F).with.a.storm.collar.(SC).and.a.floor.guide.(FG).or.ventilated.

anchor.plate.(APV).(see.Figure 36.roof/floor.penetration).

2...Those.components.allows.the.chimney.to.penetrate.a.combustible.roof.

or.floor.at.2.inches.clearance.to.combustible...See table 3.–.Minimum.

openings.for.framing.dimension.

3...The.radiant.shield.of.the.firestop.may.need.to.be.trimmed.to.fit.the.

height.of.the.roof...Nominal.height.is.10.inches.

4...Roof/floor.penetration.components.are.designed.to.be.installed.on.a.

flat.roof...They.may.be.installed.on.a.pitch.roof.if.a.curb.is.installed.

to.provide.a.flat.surface.

5...Floor.guide.is.used.to.protect.the.flashing.from.lateral.movement...The.

ventilated.anchor.plate.is.used.to.protect.the.flashing.and.to.provide.

a.re-support.

6.. Do.not.install.a.chimney.joint.or.a.expansion.length.in.the.roof/floor.

space.

7.. For.installation.on.non-combustibles.materials,.the.minimum.opening.

can.be.reduced.to.I.D...+.6.inches...The.anchor.plate.can.also.be.used.

instead.of.the.ventilated.version.

8.. Always.seal,.with.outer.joint.sealant,.between.storm.collar.and.outer.

chimney.casing.

9..Installation.step:

a..Cut.opening.to.dimensions.specify.in.table 3.

b..Install.the.Firestop.under.the.roof/floor.and.attach.it.with.screw.

c..Slide.DIS./.DAS.chimney.trough.the.firestop.

d..Install.the.floor.guide.or.the.ventilated.anchor.plate.on.top.of.the.

roof/floor.

e..Install. flashing. over. the. chimney. and. the. guide/support. and.

screw.it.

f.. The.storm.collar.is.placed.around.the.chimney.and.sealed.to.the.

casing.with.outer.joint.sealant..The.storm.collar.should.not.quite.

rest.on.the.flashing.when.the.chimney.is.cold.(1/4”.gap.between.

the.collar.and.the.top.of.the.flashing).

WALL PENETRATION

1...This.part.is.used.to.allow.model.DIS./.DAS.chimney.to.pass.trough.a.

wall.made.of.combustible.construction..

. NOTE: Crossing a combustible wall is not permitted for diameters

larger than 10” inside diameter.

2.. The.wall.penetrator.(FSW).consist.of.a.firestop.female.half.and.a.male.

half.that.slide.in.each.other.to.adjust.wall.thickness.from.7.8”.to.12.1”,.

see.Figure 37.

3...Installation.step:

a..Cut.opening.to.dimension.indicated.in.table 3.

b..Slide.the.firestop.female.half.into.the.opening.and.fix.it.to.the.

wall.with.screws.

c..On.the.other.side.of.the.wall,.slide.the.male.half.into.the.opening.

and.fix.it.

d..Insert.the.chimney.trough.the.opening.of.the.wall.firestop...Make.

sure.there.is.no.chimney.joint.or.expansion.length.in.the.wall.

opening.

e..The. chimney. section. must. be. well. supported. and. guided. to.

prevent.any.load.on.the.wall.firestop.

Figure 37 - Wall firestop

Firestop

female half

Chimney

length

Firestop

Male half

Figure 36 - Roof / floor penetration

Storm Collar (SC)

Floor guide or

ventilated anchor

plate

No joint or expansion

length in this area

Firestop radiant shield

Sealant

Flashing

2” Clearances (DIS)

4” Clearances (DAS)

Combustible

roof / floor