* MVS = Maximum Vertical Spacing between two guides or a support and

a guide in a vertical position.

** H = Maximum freestanding Height above the roof.

*** MHS = Maximum Horizontal Spacing between two guides or a support

and a guide is 12 feet.

THERMAL EXPANSION

Good installation practice requires that any length of exhaust system

between two fixed points subject to more than 1/4 inch expansion must

have an Adjustable Length (LA) or Bellows Joint (LB) to compensate

for expansion. Models DIS and DAS will expand approximately 1 inch

for every 100°F temperature rise per 100 feet of chimney. To accom-

modate chimney movements, any wall guide or floor guide must be

located away from the locking band.

It.is.essential.that.these.parts.be.properly.installed.and.provided.with.

adequate.support.and.guidance.to.prevent.binding.or.excessive.bend-

ing.forces..(See.detailed.installation.information.contained.on.page 19,.

Thermal Expansion).

6

SUPPORT METHODS AND HEIGHT LIMITS

1.. .Several.support.and.guiding.methods.are.used.to.anchor.a.chimney.

against.upward,.downward.and.angular.displacement.

2.. .These.supports.and.guides.used.with.thermal.expansion.devices,.

prevent.bending.stresses.on.the.chimney.elbows.and.joints.

3.. Supports.and.guiding.methods.and.installation.are.described.in.Sec-

tion.C..Certain.limitations.apply.for.proper.installation.of.supports.

and.guides...See tables 6 and 7.

NOTE: When the

maximum height from

table 6 is exceeded, re-

support using another

support and expansion

joint.

Figure 6 - Maximum chimney heights and support

“ M V S ” d i m e n -

sion see table 7 for

Maximum Vertical

Spacing between two

guides or a support

and a guide.

NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

SUPPORT AND GUIDE SPACING FOR MODEL DIS AND DAS

Inside

Diameter (in)

MVS*

H**

MHS***

Interior

Exterior

5

10

8

10

12

6

10

8

10

12

8

10

8

10

12

10

10

8

10

12

12

10

8

10

12

14

10

8

10

12

16

10

8

10

12

18

10

8

10

12

20

10

8

10

12

22

10

8

10

12

24

10

8

10

12

26

10

8

10

12

28

10

8

10

12

30

10

8

10

12

32

10

8

10

12

34

10

8

10

12

36

10

8

10

12

Table 7

- Dimensions are in feet

See Dim. “H” figure 7

and Chimney Guying

and Bracing in this

section.

Maximum

height - See

table 6

MVS

MVS

MVS

Termination

Storm collar (SC)
Roof support (RS)

Wall guide (WG)

Floor guide (FG)

Wall support (WS)

MAXIMUM CHIMNEY HEIGHTS AND SUPPORT METHOD FOR MODEL DIS AND DAS

Inside

Diameter

(in)

Anchor

Plate

(AP)

Anchor Plate

with Length

(APL)

Ventilated

Anchor Plate

(APV)

Wall Support (WS)

Tee

(T)

Metal Frame Only

Metal Frame

OR Wood

Frame

Metal

Frame

Wood

Frame

DIS/DAS

DIS

DAS

DIS/DAS

DIS/DAS

DIS/DAS

5

147

200

200

133

147

61

105

6

128

200

200

116

128

53

92

8

103

200

200

93

106

43

74

10

86

177

200

78

86

35

61

12

73

152

194

66

73

30

53

14

64

133

175

58

64

27

46

16

57

118

146

52

57

24

41

18

53

106

135

48

53

22

38

20

48

97

125

43

48

20

34

22

44

89

117

40

44

18

31

24

37

76

92

34

37

15

27

26

35

71

88

32

35

14

25

28

33

66

83

30

33

13

23

30

31

63

76

28

31

13

22

32

29

59

73

26

29

12

21

34

27

56

70

25

27

11

20

36

26

53

65

23

26

11

18