Figure 77 - Fan adaptor

FAN ADAPTOR PLATE (FAN) (DIS ONLY)

1....The.fan.adaptor.is.designed.to.connect.to.an.upblast.fan.mounted.

on.a.roof.curb....

2.. .When.connected.to.an.upblast.fan.(See.Figure 77),.the.plate.mounts.

on.top.of.the.fan.curb.which.supports.the.fan.housing...

3.. .The.plate.may.be.positioned.off.center.within.the.curb.provided.that.

minimum.clearance.to.combustibles.is.maintained...

4.. .In.the.event.that.the.plate.is.positioned.off.center,.trim.off.excess.

plate.material.to.allow.fan.placement...

5.. .Secure.the.plate.to.the.curb.a.minimum.of.three.(3).places.per.side.

with.minimum.#8.x.1-1/4”.wood.screws...You.will.have.to.drill.holes.

in.the.plate.

6.. .The.fan.housing.is.set.on.top.of.the.plate.and.sealed.using.S-650.

sealant.or.an.approved.gasket.supplied.by.the.fan.manufacturer...

7.. .Specify.the.chimney.diameter.and.outside.curb.dimensions.when.

ordering.the.fan.adaptor.plate.

8.. .The.fan.adaptor.plate.can.be.used.as.a.vertical.support...The.maximum.

height.of.grease.duct.supported.by.the.fan.adaptor.plate.is.15’.for.all.

diameters.

WARNING: DO NOT EXCEED THE MAXIMUM LOAD LIMIT OF THE ROOF

CURB OR THE ROOF.

MAINTENANCE

1.. .Grease.duct.is.required.by.NFPA.96.and.many.local.building.codes.

to.be.inspected.and.cleaned.if.necessary.at.specific.intervals...

2.. .Duravent.Model.DIS.Grease.Duct.must.be.inspected.and.cleaned.in.

accordance.with.local.requirements..It.requires.no.additional.internal.

maintenance..

3.. .Duravent.recommends.that.grease.containers.connected.to.drainage.

points.be.emptied.and.washed.out.daily.or.more.often,.if.necessary..

If.needed,.the.drain.nipples.should.be.checked.and.cleaned.whenever.

the.containers.are.emptied.

4.. .Where.the.duct.is.installed.outside.the.building,.the.galvalum.steel.

outer.casing.must.be.primed.and.painted..The.paint.surface.should.

be.maintained.regularly.to.prevent.possible.deterioration.of.the.casing.

surface..The.use.of.stainless.steel.outer.casing.negates.the.need.for.

painting.

NOTE: When solid fuel fired cooking appliances are vented with Model

DIS Grease Duct, creosote and grease may buildup on the inner flue.

This mixture can result in an unusually severe duct fire. To minimize fire

hazard, the duct should be inspected weekly and any residue removed by

cleaning. Additional requirements for solid fuel fired cooking appliances

are outlined in NFPA 96.

Upblast fan

Fan adaptor

Screws

(by others)

Sealant

Fan curb