X min. = EXPANSION + 3 [inch]

EXPANSION = (length[feet]/100)x(

T[°F]/100)

Operating Temp. [°F]

Max distance with one Adjustable length [feet]

200

200

300

133

400

100

500

80

800

50

1000

40

1200

33

1400

29

Table 15 :

Maximum run with Adjustable length between two fixed points

ADJUSTABLE LENGTH

1.. .The.adjustable.length.(LA).is.used.for.two.functions,.one.is.to.make.

odd.lengths.and.the.other.to.serve.as.an.expansion.joint..

2.. .The.adjustable.length.may.be.used.when.internal.pressure.do.not.

exceed.6”.water.column.or.in.well.ventilated.areas..See.Figure 66

for good.positioning.of.the.adjustable.length.

3.. .The.adjustable.length.assembly.includes.a.sliding.inner.section,.two.

containing.rings,.one.compression.band,.a.graphite.packing.gasket,.

an.insulation.band.(DIS.only).and.a.telescopic.outer.casing..There.

is.a.tool.supplied.with.this.assembly..(see.Figure 67).

4.. .For.proper.installation,.the.adjustable.length.must.have.adequate.

overlap.and.sufficient.allowance.for.thermal.expansion..(see.Figure

56.-.Adjustable.length.(LA),.and.table 15).

5.. .Installation steps (see.Figure 57):

a..Adjust.the.length.of.the.chimney.as.required...If.outer.casing.

or.inner.flue.are.too.long,.they.may.be.cut.to.length...You.must.

keep.the.overlap.of.the.outer.casing.to.at.least.1”...You.are.only.

authorised.to.cut.on.the.outer.casing.section.attached.to.the.

female.coupling..See.Figure 52.

b..Move.up.the.sliding.section.of.the.outer.wall.to.access.inner.

wall...See.Figure 53.

c..Tighten.the.compression.band.so.that.the.graphite.packing.is.

firmly.registered.against.the.inner.flue..See.Figure 54.

d..Tighten.all.the.bolts.of.the.containing.ring...For.each.bolt,.use.

the.supplied.tool.as.a.guide.between.the.two.containing.rings..

(see.Figure 55).

e..Fill.the.gap.between.the.inner.flue.and.outer.casing.with.the.

supplied.insulation.band..See.Figure 56 (DIS.only).

f.. Move.down.the.sliding.section.of.the.outer.wall.to.the.flange.of.

the.female.coupling.and.install.the.locking.band.as.described.in.

section.A:.Chimney.and.fitting.joint.assembly...See Figure 57.

Figure 58 - Adjustable length

Figure 52 -

Adjustable length

, INSTALLATION STEP A

Desired length

Figure 55 -

Adjustable length,

INSTALLATION STEP D

Supplied tool

Desired length

Move outer casing

Figure 53

- Adjustable length,

INSTALLATION STEP B

Figure 56

- Adjustable length,

INSTALLATION STEP E

Figure 57

- Adjustable length

, INSTALLATION STEP F

Figure 54 -

Adjustable length,

INSTALLATION STEP C

NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

Wrench

Compression band

Insulation band (DIS only)

Graphite packing

Containing ring

Telescopic

outer casing

1” Min.

overlap

X Min.