Figure 49 - Drain length

Drain tubing

(by others)

Drain

Drain length

Trap height equal to max

appliance outlet pressure

Figure 50 - Relief Valve installation

Flue direction

Tee 45 RV (T45RV)

Anchor plate (AP)

in frame by others

ANSI Female Flange adaptor (FFA)

Relief valve

NOTE:.DIAGRAMS.&.ILLUSTRATIONS.ARE.NOT.TO.SCALE.

20

DRAIN LENGTH

Drain Length (DL)

1.....Used.to.drain.rain.or.condensate.from.the.chimney.

2.....The.chimney.flue.is.equipped.with.an.annular.catch.ring.and.a.1”.NPT.

nipple.extending.through.the.outer.casing.for.attachment.of.drain.

tubing.

3.....The.drain.tubing.should.include.a.water.trap.of.a.height.at.least.equal.

to.the.maximum.expected.operating.pressure.at.the.appliance.outlet.

to.avoid.allowing.flue.gases.to.vent.through.the.drain..See.Figure 49.

4.....Drain.length.should.be.installed.indoors.to.prevent.freezing.

RELIEF VALVE (DIS ONLY)

Relief Valve (RV)

1.....The.relief.valve.is.intended.for.use.with.diesel.engines.to.provide.extra.

protection.to.the.chimney.in.case.of.a.delayed.ignition.of.backfire.

2.....The.connection.of.the.Relief.valve.and.the.DIS.chimney.is.done.with.

the.use.of.the.ANSI.Female.Flange.Adaptor.(FFA).

3.....The.valve.is.factory.calibrated.to.open.at.27.in..wc.

4.....The.relief.valve.must.be.supported.independently.of.the.rest.of.the.

exhaust.system...The.best.way.to.accomplish.this.is.to.locate.an.

Anchor. Plate. (AP). support. at. the. joint. between. the. ANSI. Flange.

adaptor.and.the.adjacent.fitting..See.Figure 50.

5.....It.is.crucial.that.the.support.be.properly.secured.to.building.structure.

so.that.it.can.withstand.the.forces.generated.in.case.of.delayed.fuel.

ignition.

6.......It.must.be.installed.in.combination.with.a.Tee.45°.Relief.Valve.(T45RV).

Figure 47 - Flip Top (FT)

Figure 48 - Miter Cut Termination (MC)

Flip top

Bird screen

Figure 46 - Finishing Cone (FC)

Better draft