40317650.01 09/2010 GB/D/F/E/I
4. Specifications and intended use
4. Specifications and intended use
Accuracy
Linearisation error: ±1.0 % FS
Measuring accuracy at 0 … +50 °C: ±3.0 % FS
at -10 … +50 °C: ±5.0 % FS
Typical overall error: ±2.0 % FS
Measuring ranges
0 … 250 Pa, 0 … 500 Pa, 0 … 750 Pa, 0 … 1000 Pa,
0 … 1250 Pa, 0 … 2500 Pa, 0 … 3750 Pa, 0 … 5000 Pa
Maximum pressure
0 … 250 to 0 … 750 Pa:
5 kPa
0 … 1000 to 0 … 5000 Pa: 5 x FS
Burst pressure
0 … 250 to 0 … 750 Pa:
10 kPa
0 … 1000 to 0 … 5000 Pa: 10 x FS
Operating temperature
Storage: -20 … +85 °C
Operation: -10 … +50 °C
Ingress protection
IP 65 per EN 60529 / lEC 529
Standards
CE conformity:
89/336/EEC Electromagnetic Compatibility
2002/95/EG RoHS (restriction of the use of certain hazardous
substances in electrical and electronic equipment)